home *** CD-ROM | disk | FTP | other *** search
Text File | 1993-08-26 | 58.1 KB | 1,306 lines |
- /* Part 2 of 4 of the builidng requirments follows. */
- 4.1.7 Accessible Buildings: Historic Preservation.
-
- (1) Applicability:
-
- (a) General Rule. Alterations to a qualified historic
- building or facility shall comply with 4.1.6 Accessible
- Buildings: Alterations, the applicable technical specifications
- of 4.2 through 4.35 and the applicable special application
- sections 5 through 10 unless it is determined in accordance with
- the procedures in 4.1.7(2) that compliance with the requirements
- for accessible routes (exterior and interior), ramps, entrances,
- or toilets would threaten or destroy the historic significance of
- the building or facility in which case the alternative
- requirements in 4.1.7(3) may be used for the feature.
-
- EXCEPTION: (Reserved).
-
- (b) Definition. A qualified historic building or facility
- is a building or facility that is:
-
- (i) Listed in or eligible for listing in the National
- Register of Historic Places; or
-
- (ii) Designated as historic under an appropriate State or
- local law.
-
- (2) Procedures:
-
- (a) Alterations to Qualified Historic Buildings and
-
- Facilities Subject to Section 106 of the National Historic
- Preservation Act:
-
- (i) Section 106 Process. Section 106 of the National
- Historic Preservation Act (16 U.S.C. 470 f) requires that a
- Federal agency with jurisdiction over a Federal, federally
- assisted, or federally licensed undertaking consider the effects
- of the agency's undertaking on buildings and facilities listed in
- or eligible for listing in the National Register of Historic
- Places and give the Advisory Council on Historic Preservation a
- reasonable opportunity to comment on the undertaking prior to
- approval of the undertaking.
-
- (ii) ADA Application. Where alterations are undertaken
- to a qualified historic building or facility that is subject to
- section 106 of the National Historic Preservation Act, the
- Federal agency with jurisdiction over the undertaking shall
- follow the section 106 process. If the State Historic
- Preservation Officer or Advisory Council on Historic Preservation
- agrees that compliance with the requirements for accessible
- routes (exterior and interior), ramps, entrances, or toilets
- would threaten or destroy the historic significance of the
- building or facility, the alternative requirements in 4.1.7(3)
- may be used for the feature.
-
- (b) Alterations to Qualified Historic Buildings and
- Facilities Not Subject to Section 106 of the National Historic
- Preservation Act. Where alterations are undertaken to a
- qualified historic building or facility that is not subject to
- section 106 of the National Historic Preservation Act, if the
- entity undertaking the alterations believes that compliance with
- the requirements for accessible routes (exterior and interior),
- ramps, entrances, or toilets would threaten or destroy the
- historic significance of the building or facility and that the
- alternative requirements in 4.1.7(3) should be used for the
- feature, the entity should consult with the State Historic
- Preservation Officer. If the State Historic Preservation Officer
- agrees that compliance with the accessibility requirements for
- accessible routes (exterior and interior), ramps, entrances or
- toilets would threaten or destroy the historical significance of
- the building or facility, the alternative requirements in
- 4.1.7(3) may be used.
-
- (c) Consultation With Interested Persons. Interested
- persons should be invited to participate in the consultation
- process, including State or local accessibility officials,
- individuals with disabilities, and organizations representing
- individuals with disabilities.
-
- (d) Certified Local Government Historic Preservation
- Programs. Where the State Historic Preservation Officer has
- delegated the consultation responsibility for purposes of this
- section to a local government historic preservation program that
- has been certified in accordance with section 101(c) of the
- National Historic Preservation Act of 1966 (16 U.S.C. 470a (c))
- and implementing regulations (36 CFR 61.5), the responsibility
- may be carried out by the appropriate local government body or
- official.
-
- (3) Historic Preservation: Minimum Requirements:
-
- (a) At least one accessible route complying with 4.3 from
- a site access point to an accessible entrance shall be provided.
-
- EXCEPTION: A ramp with a slope no greater than 1:6 for a run not
- to exceed 2 ft (610 mm) may be used as part of an accessible
- route to an entrance.
-
- (b) At least one accessible entrance complying with 4.14
- which is used by the public shall be provided.
-
- EXCEPTION: If it is determined that no entrance used by the
- public can comply with 4.14, then access at any entrance not used
- by the general public but open (unlocked) with directional
- signage at the primary entrance may be used. The accessible
- entrance shall also have a notification system. Where security
- is a problem, remote monitoring may be used.
-
- (c) If toilets are provided, then at least one toilet
- facility complying with 4.22 and 4.1.6 shall be provided along an
- accessible route that complies with 4.3. Such toilet facility
- may be unisex in design.
-
- (d) Accessible routes from an accessible entrance to all
- publicly used spaces on at least the level of the accessible
- entrance shall be provided. Access shall be provided to all
- levels of a building or facility in compliance with 4.1 whenever
- practical.
-
- (e) Displays and written information, documents, etc.,
- should be located where they can be seen by a seated person.
- Exhibits and signage displayed horizontally (e.g., open books),
- should be no higher than 44 in (1120 mm) above the floor surface.
-
- NOTE: The technical provisions of sections 4.2 through 4.35 are
- the same as those of the American National Standard Institute's
- document A117.1-1980, except as noted in the text.
-
- 4.2 Space Allowance and Reach Ranges.
-
- 4.2.1* Wheelchair Passage Width. The minimum clear width for
- single wheelchair passage shall be 32 in (815 mm) at a point and
- 36 in (915 mm) continuously (see Fig. 1 and 24(e)).
-
- 4.2.2 Width for Wheelchair Passing. The minimum width for two
- wheelchairs to pass is 60 in (1525 mm) (see Fig. 2).
-
- 4.2.3* Wheelchair Turning Space. The space required for a
- wheelchair to make a 180-degree turn is a clear space of 60 in
- (1525 mm) diameter (see Fig. 3(a)) or a T-shaped space (see Fig.
- 3(b)).
-
- 4.2.4* Clear Floor or Ground Space for Wheelchairs.
-
- 4.2.4.1 Size and Approach. The minimum clear floor or ground
- space required to accommodate a single, stationary wheelchair and
- occupant is 30 in by 48 in (760 mm by 1220 mm) (see Fig. 4(a)).
- The minimum clear floor or ground space for wheelchairs may be
- positioned for forward or parallel approach to an object (see
- Fig. 4(b) and (c)). Clear floor or ground space for wheelchairs
- may be part of the knee space required under some objects.
-
- 4.2.4.2 Relationship of Maneuvering Clearance to Wheelchair
- Spaces. One full unobstructed side of the clear floor or ground
- space for a wheelchair shall adjoin or overlap an accessible
- route or adjoin another wheelchair clear floor space. If a clear
- floor space is located in an alcove or otherwise confined on all
- or part of three sides, additional maneuvering clearances shall
- be provided as shown in Fig. 4(d) and (e).
-
- 4.2.4.3 Surfaces for Wheelchair Spaces. Clear floor or ground
- spaces for wheelchairs shall comply with 4.5.
-
- 4.2.5* Forward Reach. If the clear floor space only allows
- forward approach to an object, the maximum high forward reach
- allowed shall be 48 in (1220 mm) (see Fig. 5(a)). The minimum
- low forward reach is 15 in (380 mm). If the high forward reach
- is over an obstruction, reach and clearances shall be as shown in
- Fig. 5(b).
-
- 4.2.6* Side Reach. If the clear floor space allows parallel
- approach by a person in a wheelchair, the maximum high side reach
- allowed shall be 54 in (1370 mm) and the low side reach shall be
- no less than 9 in (230 mm) above the floor (Fig. 6(a) and (b)).
- If the side reach is over an obstruction, the reach and
- clearances shall be as shown in Fig 6(c).
-
- 4.3 Accessible Route.
-
- 4.3.1* General. All walks, halls, corridors, aisles, skywalks,
- tunnels, and other spaces that are part of an accessible route
- shall comply with 4.3.
-
- 4.3.2 Location.
-
- (1) At least one accessible route within the boundary of
- the site shall be provided from public transportation stops,
- accessible parking, and accessible passenger loading zones, and
- public streets or sidewalks to the accessible building entrance
- they serve. The accessible route shall, to the maximum extent
- feasible, coincide with the route for the general public.
-
- (2) At least one accessible route shall connect accessible
- buildings, facilities, elements, and spaces that are on the same
- site.
-
- (3) At least one accessible route shall connect accessible
- building or facility entrances with all accessible spaces and
- elements and with all accessible dwelling units within the
- building or facility.
-
- (4) An accessible route shall connect at least one
- accessible entrance of each accessible dwelling unit with those
- exterior and interior spaces and facilities that serve the
- accessible dwelling unit.
-
- 4.3.3 Width. The minimum clear width of an accessible route
- shall be 36 in (915 mm) except at doors (see 4.13.5 and 4.13.6).
- If a person in a wheelchair must make a turn around an
- obstruction, the minimum clear width of the accessible route
- shall be as shown in Fig. 7(a) and (b).
-
- 4.3.4 Passing Space. If an accessible route has less than 60 in
- (1525 mm) clear width, then passing spaces at least 60 in by 60
- in (1525 mm by 1525 mm) shall be located at reasonable intervals
- not to exceed 200 ft (61 m). A T-intersection of two corridors
- or walks is an acceptable passing place.
-
- 4.3.5 Head Room. Accessible routes shall comply with 4.4.2.
-
- 4.3.6 Surface Textures. The surface of an accessible route shall
- comply with 4.5.
-
- 4.3.7 Slope. An accessible route with a running slope greater
- than 1:20 is a ramp and shall comply with 4.8. Nowhere shall the
- cross slope of an accessible route exceed 1:50.
-
- 4.3.8 Changes in Levels. Changes in levels along an accessible
- route shall comply with 4.5.2. If an accessible route has
- changes in level greater than 1/2 in (13 mm), then a curb ramp,
- ramp, elevator, or platform lift (as permitted in 4.1.3 and
- 4.1.6) shall be provided that complies with 4.7, 4.8, 4.10, or
- 4.11, respectively. An accessible route does not include stairs,
- steps, or escalators. See definition of "egress, means of" in
- 3.5.
-
- 4.3.9 Doors. Doors along an accessible route shall comply with
- 4.13.
-
- 4.3.10* Egress. Accessible routes serving any accessible space
- or element shall also serve as a means of egress for emergencies
- or connect to an accessible area of rescue assistance.
-
- 4.3.11 Areas of Rescue Assistance.
-
- 4.3.11.1 Location and Construction. An area of rescue assistance
- shall be one of the following:
-
- (1) A portion of a stairway landing within a smokeproof
- enclosure (complying with local requirements).
-
- (2) A portion of an exterior exit balcony located
- immediately adjacent to an exit stairway when the balcony
- complies with local requirements for exterior exit balconies.
- Openings to the interior of the building located within 20 feet
- (6 m) of the area of rescue assistance shall be protected with
- fire assemblies having a three- fourths hour fire protection
- rating.
-
- (3) A portion of a one-hour fire-resistive corridor
- (complying with local requirements for fire-resistive
- construction and for openings) located immediately adjacent to an
- exit enclosure.
-
- (4) A vestibule located immediately adjacent to an exit
- enclosure and constructed to the same fire-resistive standards as
- required for corridors and openings.
-
- (5) A portion of a stairway landing within an exit
- enclosure which is vented to the exterior and is separated from
- the interior of the building with not less than one-hour
- fire-resistive doors.
-
- (6) When approved by the appropriate local authority, an
- area or a room which is separated from other portions of the
- building by a smoke barrier. Smoke barriers shall have a
- fire-resistive rating of not less than one hour and shall
- completely enclose the area or room. Doors in the smoke barrier
- shall be tight-fitting smoke- and draft-control assemblies having
- a fire-protection rating of not less than 20 minutes and shall be
- self-closing or automatic closing. The area or room shall be
- provided with an exit directly to an exit enclosure. Where the
- room or area exits into an exit enclosure which is required to be
- of more than one-hour fire- resistive construction, the room or
- area shall have the same fire- resistive construction, including
- the same opening protection, as required for the adjacent exit
- enclosure.
-
- (7) An elevator lobby when elevator shafts and adjacent
- lobbies are pressurized as required for smokeproof enclosures by
- local regulations and when complying with requirements herein for
- size, communication, and signage. Such pressurization system
- shall be activated by smoke detectors on each floor located in a
- manner approved by the appropriate local authority.
- Pressurization equipment and its duct work within the building
- shall be separated from other portions of the building by a
- minimum two-hour fire- resistive construction.
-
- 4.3.11.2 Size. Each area of rescue assistance shall provide at
- least two accessible areas each being not less than 30 inches by
- 48 inches (760 mm by 1220 mm). The area of rescue assistance
- shall not encroach on any required exit width. The total number
- of such 30-inch by 48-inch (760 mm by 1220 mm) areas per story
- shall be not less than one for every 200 persons of calculated
- occupant load served by the area of rescue assistance.
-
- EXCEPTION: The appropriate local authority may reduce the minimum
- number of 30-inch by 48-inch (760 mm by 1220 mm) areas to one for
- each area of rescue assistance on floors where the occupant load
- is less than 200.
-
- 4.3.11.3* Stairway Width. Each stairway adjacent to an area of
- rescue assistance shall have a minimum clear width of 48 inches
- between handrails.
-
- 4.3.11.4* Two-way Communication. A method of two-way
- communication, with both visible and audible signals, shall be
- provided between each area of rescue assistance and the primary
- entry. The fire department or appropriate local authority may
- approve a location other than the primary entry.
-
- 4.3.11.5 Identification. Each area of rescue assistance shall be
- identified by a sign which states "AREA OF RESCUE ASSISTANCE" and
- displays the international symbol of accessibility. The sign
- shall be illuminated when exit sign illumination is required.
- Signage shall also be installed at all inaccessible exits and
- where otherwise necessary to clearly indicate the direction to
- areas of rescue assistance. In each area of rescue assistance,
- instructions on the use of the area under emergency conditions
- shall be posted adjoining the two-way communication system.
-
- 4.4 Protruding Objects.
-
- 4.4.1* General. Objects projecting from walls (for example,
- telephones) with their leading edges between 27 in and 80 in (685
- mm and 2030 mm) above the finished floor shall protrude no more
- than 4 in (100 mm) into walks, halls, corridors, passageways, or
- aisles (see Fig. 8(a)). Objects mounted with their leading edges
- at or below 27 in (685 mm) above the finished floor may protrude
- any amount (see Fig. 8(a) and (b)). Free-standing objects
- mounted on posts or pylons may overhang 12 in (305 mm) maximum
- from 27 in to 80 in (685 mm to 2030 mm) above the ground or
- finished floor (see Fig. 8(c) and (d)). Protruding objects shall
- not reduce the clear width of an accessible route or maneuvering
- space (see Fig. 8(e)).
-
- 4.4.2 Head Room. Walks, halls, corridors, passageways, aisles,
- or other circulation spaces shall have 80 in (2030 mm) minimum
- clear head room (see Fig. 8(a)). If vertical clearance of an
- area adjoining an accessible route is reduced to less than 80 in
- (nominal dimension), a barrier to warn blind or visually-impaired
- persons shall be provided (see Fig. 8(c-1)).
-
- 4.5 Ground and Floor Surfaces.
-
- 4.5.1* General. Ground and floor surfaces along accessible
- routes and in accessible rooms and spaces including floors,
- walks, ramps, stairs, and curb ramps, shall be stable, firm,
- slip-resistant, and shall comply with 4.5.
-
- 4.5.2 Changes in Level. Changes in level up to 1/4 in (6 mm) may
- be vertical and without edge treatment (see Fig. 7(c) ). Changes
- in level between 1/4 in and 1/2 in (6 mm and 13 mm) shall be
- beveled with a slope no greater than 1:2 (see Fig. 7(d) ).
- Changes in level greater than 1/2 in (13 mm) shall be
- accomplished by means of a ramp that complies with 4.7 or 4.8.
-
- 4.5.3* Carpet. If carpet or carpet tile is used on a ground or
- floor surface, then it shall be securely attached; have a firm
- cushion, pad, or backing, or no cushion or pad; and have a level
- loop, textured loop, level cut pile, or level cut/uncut pile
- texture. The maximum pile thickness shall be 1/2 in (13 mm) (see
- Fig. 8(f)). Exposed edges of carpet shall be fastened to floor
- surfaces and have trim along the entire length of the exposed
- edge. Carpet edge trim shall comply with 4.5.2.
-
- 4.5.4 Gratings. If gratings are located in walking surfaces,
- then they shall have spaces no greater than 1/2 in (13 mm) wide
- in one direction (see Fig. 8(g)). If gratings have elongated
- openings, then they shall be placed so that the long dimension is
- perpendicular to the dominant direction of travel (see Fig.
- 8(h)).
-
- 4.6 Parking and Passenger Loading Zones.
-
- 4.6.1 Minimum Number. Parking spaces required to be accessible
- by 4.1 shall comply with 4.6.2 through 4.6.5. Passenger loading
- zones required to be accessible by 4.1 shall comply with 4.6.5
- and 4.6.6.
-
- 4.6.2 Location. Accessible parking spaces serving a particular
- building shall be located on the shortest accessible route of
- travel from adjacent parking to an accessible entrance. In
- parking facilities that do not serve a particular building,
- accessible parking shall be located on the shortest accessible
- route of travel to an accessible pedestrian entrance of the
- parking facility. In buildings with multiple accessible
- entrances with adjacent parking, accessible parking spaces shall
- be dispersed and located closest to the accessible entrances.
-
- 4.6.3* Parking Spaces. Accessible parking spaces shall be at
- least 96 in (2440 mm) wide. Parking access aisles shall be part
- of an accessible route to the building or facility entrance and
- shall comply with 4.3. Two accessible parking spaces may share a
- common access aisle (see Fig. 9). Parked vehicle overhangs shall
- not reduce the clear width of an accessible route. Parking
- spaces and access aisles shall be level with surface slopes not
- exceeding 1:50 (2%) in all directions.
-
- 4.6.4* Signage. Accessible parking spaces shall be designated as
- reserved by a sign showing the symbol of accessibility (see
- 4.30.7). Spaces complying with 4.1.2(5)(b) shall have an
- additional sign "Van-Accessible" mounted below the symbol of
- accessibility. Such signs shall be located so they cannot be
- obscured by a vehicle parked in the space.
-
- 4.6.5* Vertical Clearance. Provide minimum vertical clearance of
- 114 in (2895 mm) at accessible passenger loading zones and along
- at least one vehicle access route to such areas from site
- entrance(s) and exit(s). At parking spaces complying with
- 4.1.2(5)(b), provide minimum vertical clearance of 98 in (2490
- mm) at the parking space and along at least one vehicle access
- route to such spaces from site entrance(s) and exit(s).
-
- 4.6.6 Passenger Loading Zones. Passenger loading zones shall
- provide an access aisle at least 60 in (1525 mm) wide and 20 ft
- (240 in)(6100 mm) long adjacent and parallel to the vehicle
- pull-up space (see Fig. 10). If there are curbs between the
- access aisle and the vehicle pull-up space, then a curb ramp
- complying with 4.7 shall be provided. Vehicle standing spaces
- and access aisles shall be level with surface slopes not
- exceeding 1:50 (2%) in all directions.
-
- 4.7 Curb Ramps.
-
- 4.7.1 Location. Curb ramps complying with 4.7 shall be provided
- wherever an accessible route crosses a curb.
-
- 4.7.2 Slope. Slopes of curb ramps shall comply with 4.8.2. The
- slope shall be measured as shown in Fig. 11. Transitions from
- ramps to walks, gutters, or streets shall be flush and free of
- abrupt changes. Maximum slopes of adjoining gutters, road
- surface immediately adjacent to the curb ramp, or accessible
- route shall not exceed 1:20.
-
- 4.7.3 Width. The minimum width of a curb ramp shall be 36 in
- (915 mm), exclusive of flared sides.
-
- 4.7.4 Surface. Surfaces of curb ramps shall comply with 4.5.
-
- 4.7.5 Sides of Curb Ramps. If a curb ramp is located where
- pedestrians must walk across the ramp, or where it is not
- protected by handrails or guardrails, it shall have flared sides;
- the maximum slope of the flare shall be 1:10 (see Fig. 12(a)).
- Curb ramps with returned curbs may be used where pedestrians
- would not normally walk across the ramp (see Fig. 12(b)).
-
- 4.7.6 Built-up Curb Ramps. Built-up curb ramps shall be located
- so that they do not project into vehicular traffic lanes (see
- Fig. 13).
-
- 4.7.7 Detectable Warnings. A curb ramp shall have a detectable
- warning complying with 4.29.2. The detectable warning shall
- extend the full width and depth of the curb ramp.
-
- 4.7.8 Obstructions. Curb ramps shall be located or protected to
- prevent their obstruction by parked vehicles.
-
- 4.7.9 Location at Marked Crossings. Curb ramps at marked
- crossings shall be wholly contained within the markings,
- excluding any flared sides (see Fig. 15).
-
- 4.7.10 Diagonal Curb Ramps. If diagonal (or corner type) curb
- ramps have returned curbs or other well-defined edges, such edges
- shall be parallel to the direction of pedestrian flow. The
- bottom of diagonal curb ramps shall have 48 in (1220 mm) minimum
- clear space as shown in Fig. 15(c) and (d). If diagonal curb
- ramps are provided at marked crossings, the 48 in (1220 mm) clear
- space shall be within the markings (see Fig. 15(c) and (d)). If
- diagonal curb ramps have flared sides, they shall also have at
- least a 24 in (610 mm) long segment of straight curb located on
- each side of the curb ramp and within the marked crossing (see
- Fig. 15(c)).
-
- 4.7.11 Islands. Any raised islands in crossings shall be cut
- through level with the street or have curb ramps at both sides
- and a level area at least 48 in (1220 mm) long between the curb
- ramps in the part of the island intersected by the crossings (see
- Fig. 15(a) and (b)).
-
- 4.8 Ramps.
-
- 4.8.1* General. Any part of an accessible route with a slope
- greater than 1:20 shall be considered a ramp and shall comply
- with 4.8.
-
- 4.8.2* Slope and Rise. The least possible slope shall be used
- for any ramp. The maximum slope of a ramp in new construction
- shall be 1:12. The maximum rise for any run shall be 30 in (760
- mm) (see Fig. 16). Curb ramps and ramps to be constructed on
- existing sites or in existing buildings or facilities may have
- slopes and rises as allowed in 4.1.6(3)(a) if space limitations
- prohibit the use of a 1:12 slope or less.
-
- 4.8.3 Clear Width. The minimum clear width of a ramp shall be 36
- in (915 mm).
-
- 4.8.4* Landings. Ramps shall have level landings at bottom and
- top of each ramp and each ramp run. Landings shall have the
- following features:
-
- (1) The landing shall be at least as wide as the ramp run
- leading to it.
-
- (2) The landing length shall be a minimum of 60 in (1525
- mm) clear.
-
- (3) If ramps change direction at landings, the minimum
- landing size shall be 60 in by 60 in (1525 mm by 1525 mm).
-
- (4) If a doorway is located at a landing, then the area in
- front of the doorway shall comply with 4.13.6.
-
- 4.8.5* Handrails. If a ramp run has a rise greater than 6 in
- (150 mm) or a horizontal projection greater than 72 in (1830 mm),
- then it shall have handrails on both sides. Handrails are not
- required on curb ramps or adjacent to seating in assembly areas.
- Handrails shall comply with 4.26 and shall have the following
- features:
-
- (1) Handrails shall be provided along both sides of ramp
- segments. The inside handrail on switchback or dogleg ramps
- shall always be continuous.
-
- (2) If handrails are not continuous, they shall extend at
- least 12 in (305 mm) beyond the top and bottom of the ramp
- segment and shall be parallel with the floor or ground surface
- (see Fig. 17).
-
- (3) The clear space between the handrail and the wall
- shall be 1
- - 1/2 in (38 mm).
-
- (4) Gripping surfaces shall be continuous.
-
- (5) Top of handrail gripping surfaces shall be mounted
- between 34 in and 38 in (865 mm and 965 mm) above ramp surfaces.
-
- (6) Ends of handrails shall be either rounded or returned
- smoothly to floor, wall, or post.
-
- (7) Handrails shall not rotate within their fittings.
-
- 4.8.6 Cross Slope and Surfaces. The cross slope of ramp surfaces
- shall be no greater than 1:50. Ramp surfaces shall comply with
- 4.5.
-
- 4.8.7 Edge Protection. Ramps and landings with drop-offs shall
- have curbs, walls, railings, or projecting surfaces that prevent
- people from slipping off the ramp. Curbs shall be a minimum of 2
- in (50 mm) high (see Fig. 17).
-
- 4.8.8 Outdoor Conditions. Outdoor ramps and their approaches
- shall be designed so that water will not accumulate on walking
- surfaces.
-
- 4.9 Stairs.
-
- 4.9.1* Minimum Number. Stairs required to be accessible by 4.1
- shall comply with 4.9.
-
- 4.9.2 Treads and Risers. On any given flight of stairs, all
- steps shall have uniform riser heights and uniform tread widths.
- Stair treads shall be no less than 11 in (280 mm) wide, measured
- from riser to riser (see Fig. 18(a)). Open risers are not
- permitted.
-
- 4.9.3 Nosings. The undersides of nosings shall not be abrupt.
- The radius of curvature at the leading edge of the tread shall be
- no greater than 1/2 in (13 mm). Risers shall be sloped or the
- underside of the nosing shall have an angle not less than 60
- degrees from the horizontal. Nosings shall project no more than
- 1-1/2 in (38 mm) (see Fig. 18).
-
- 4.9.4 Handrails. Stairways shall have handrails at both sides of
- all stairs. Handrails shall comply with 4.26 and shall have the
- following features:
-
- (1) Handrails shall be continuous along both sides of
- stairs. The inside handrail on switchback or dogleg stairs shall
- always be continuous (see Fig. 19(a) and (b)).
-
- (2) If handrails are not continuous, they shall extend at
- least 12 in (305 mm) beyond the top riser and at least 12 in (305
- mm) plus the width of one tread beyond the bottom riser. At the
- top, the extension shall be parallel with the floor or ground
- surface. At the bottom, the handrail shall continue to slope for
- a distance of the width of one tread from the bottom riser; the
- remainder of the extension shall be horizontal (see Fig. 19(c)
- and (d)). Handrail extensions shall comply with 4.4.
-
- (3) The clear space between handrails and wall shall be
- 1-1/2 in (38 mm).
-
- (4) Gripping surfaces shall be uninterrupted by newel
- posts, other construction elements, or obstructions.
-
- (5) Top of handrail gripping surface shall be mounted
- between 34 in and 38 in (865 mm and 965 mm) above stair nosings.
-
- (6) Ends of handrails shall be either rounded or returned
- smoothly to floor, wall or post.
-
- (7) Handrails shall not rotate within their fittings.
-
- 4.9.5 Detectable Warnings at Stairs. (Reserved).
-
- 4.9.6 Outdoor Conditions. Outdoor stairs and their approaches
- shall be designed so that water will not accumulate on walking
- surfaces.
-
- 4.10 Elevators.
-
- 4.10.1 General. Accessible elevators shall be on an accessible
- route and shall comply with 4.10 and with the ASME A17.1-1990,
- Safety Code for Elevators and Escalators. Freight elevators
- shall not be considered as meeting the requirements of this
- section unless the only elevators provided are used as
- combination passenger and freight elevators for the public and
- employees.
-
- 4.10.2 Automatic Operation. Elevator operation shall be
- automatic. Each car shall be equipped with a self-leveling
- feature that will automatically bring the car to floor landings
- within a tolerance of 1/2 in (13 mm) under rated loading to zero
- loading conditions. This self-leveling feature shall be
- automatic and independent of the operating device and shall
- correct the overtravel or undertravel.
-
- 4.10.3 Hall Call Buttons. Call buttons in elevator lobbies and
- halls shall be centered at 42 in (1065 mm) above the floor. Such
- call buttons shall have visual signals to indicate when each call
- is registered and when each call is answered. Call buttons shall
- be a minimum of 3/4 in (19 mm) in the smallest dimension. The
- button designating the up direction shall be on top. (See Fig.
- 20.) Buttons shall be raised or flush. Objects mounted beneath
- hall call buttons shall not project into the elevator lobby more
- than 4 in (100 mm).
-
- 4.10.4 Hall Lanterns. A visible and audible signal shall be
- provided at each hoistway entrance to indicate which car is
- answering a call. Audible signals shall sound once for the up
- direction and twice for the down direction or shall have verbal
- annunciators that say "up" or "down." Visible signals shall have
- the following features:
-
- (1) Hall lantern fixtures shall be mounted so that their
- centerline is at least 72 in (1830 mm) above the lobby floor.
- (See Fig. 20.)
-
- (2) Visual elements shall be at least 2-1/2 in (64 mm) in
- the smallest dimension.
-
- (3) Signals shall be visible from the vicinity of the hall
- call button (see Fig. 20). In-car lanterns located in cars,
- visible from the vicinity of hall call buttons, and conforming to
- the above requirements, shall be acceptable.
-
- 4.10.5 Raised and Braille Characters on Hoistway Entrances. All
- elevator hoistway entrances shall have raised and Braille floor
- designations provided on both jambs. The centerline of the
- characters shall be 60 in (1525 mm) above finish floor. Such
- characters shall be 2 in (50 mm) high and shall comply with
- 4.30.4. Permanently applied plates are acceptable if they are
- permanently fixed to the jambs. (See Fig. 20).
-
- 4.10.6* Door Protective and Reopening Device. Elevator doors
- shall open and close automatically. They shall be provided with
- a reopening device that will stop and reopen a car door and
- hoistway door automatically if the door becomes obstructed by an
- object or person. The device shall be capable of completing
- these operations without requiring contact for an obstruction
- passing through the opening at heights of 5 in and 29 in (125 mm
- and 735 mm) above finish floor (see Fig. 20). Door reopening
- devices shall remain effective for at least 20 seconds. After
- such an interval, doors may close in accordance with the
- requirements of ASME A17.1-1990.
-
- 4.10.7* Door and Signal Timing for Hall Calls. The minimum
- acceptable time from notification that a car is answering a call
- until the doors of that car start to close shall be calculated
- from the following equation:
-
- T = D/(1.5 ft/s) or T = D/(445 mm/s)
-
- where T total time in seconds and D distance (in feet or
- millimeters) from a point in the lobby or corridor 60 in (1525
- mm) directly in front of the farthest call button controlling
- that car to the centerline of its hoistway door (see Fig. 21).
- For cars with in-car lanterns, T begins when the lantern is
- visible from the vicinity of hall call buttons and an audible
- signal is sounded. The minimum acceptable notification time
- shall be 5 seconds.
-
- 4.10.8 Door Delay for Car Calls. The minimum time for elevator
- doors to remain fully open in response to a car call shall be 3
- seconds.
-
- 4.10.9 Floor Plan of Elevator Cars. The floor area of elevator
- cars shall provide space for wheelchair users to enter the car,
- maneuver within reach of controls, and exit from the car.
- Acceptable door opening and inside dimensions shall be as shown
- in Fig. 22. The clearance between the car platform sill and the
- edge of any hoistway landing shall be no greater than 1-1/4 in
- (32 mm).
-
- 4.10.10 Floor Surfaces. Floor surfaces shall comply with 4.5.
-
- 4.10.11 Illumination Levels. The level of illumination at the
- car controls, platform, and car threshold and landing sill shall
- be at least 5 footcandles (53.8 lux).
-
- 4.10.12* Car Controls. Elevator control panels shall have the
- following features:
-
- (1) Buttons. All control buttons shall be at least 3/4 in
- (19 mm) in their smallest dimension. They shall be raised or
- flush.
-
- (2) Tactile, Braille, and Visual Control Indicators. All
- control buttons shall be designated by Braille and by raised
- standard alphabet characters for letters, arabic characters for
- numerals, or standard symbols as shown in Fig. 23(a), and as
- required in ASME A17.1-1990. Raised and Braille characters and
- symbols shall comply with 4.30. The call button for the main
- entry floor shall be designated by a raised star at the left of
- the floor designation (see Fig. 23(a)). All raised designations
- for control buttons shall be placed immediately to the left of
- the button to which they apply. Applied plates, permanently
- attached, are an acceptable means to provide raised control
- designations. Floor buttons shall be provided with visual
- indicators to show when each call is registered. The visual
- indicators shall be extinguished when each call is answered.
-
- (3) Height. All floor buttons shall be no higher than 54
- in (1370 mm) above the finish floor for side approach and 48 in
- (1220 mm) for front approach. Emergency controls, including the
- emergency alarm and emergency stop, shall be grouped at the
- bottom of the panel and shall have their centerlines no less than
- 35 in (890 mm) above the finish floor (see Fig. 23(a) and (b)).
- (4) Location. Controls shall be located on a front wall
- if cars have center opening doors, and at the side wall or at the
- front wall next to the door if cars have side opening doors (see
- Fig. 23(c) and (d)).
-
- 4.10.13* Car Position Indicators. In elevator cars, a visual car
- position indicator shall be provided above the car control panel
- or over the door to show the position of the elevator in the
- hoistway. As the car passes or stops at a floor served by the
- elevators, the corresponding numerals shall illuminate, and an
- audible signal shall sound. Numerals shall be a minimum of 1/2
- in (13 mm) high. The audible signal shall be no less than 20
- decibels with a frequency no higher than 1500 Hz. An automatic
- verbal announcement of the floor number at which a car stops or
- which a car passes may be substituted for the audible signal.
-
- 4.10.14* Emergency Communications. If provided, emergency
- two-way communication systems between the elevator and a point
- outside the hoistway shall comply with ASME A17.1-1990. The
- highest operable part of a two-way communication system shall be
- a maximum of 48 in (1220 mm) from the floor of the car. It shall
- be identified by a raised symbol and lettering complying with
- 4.30 and located adjacent to the device. If the system uses a
- handset then the length of the cord from the panel to the handset
- shall be at least 29 in (735 mm). If the system is located in a
- closed compartment the compartment door hardware shall conform to
- 4.27, Controls and Operating Mechanisms. The emergency
- intercommunication system shall not require voice communication.
-
- 4.11 Platform Lifts (Wheelchair Lifts).
-
- 4.11.1 Location. Platform lifts (wheelchair lifts) permitted by
- 4.1 shall comply with the requirements of 4.11.
-
- 4.11.2* Other Requirements. If platform lifts (wheelchair lifts)
- are used, they shall comply with 4.2.4, 4.5, 4.27, and ASME A17.1
- Safety Code for Elevators and Escalators, Section XX, 1990.
-
- 4.11.3 Entrance. If platform lifts are used then they shall
- facilitate unassisted entry, operation, and exit from the lift in
- compliance with 4.11.2.
-
- 4.12 Windows.
-
- 4.12.1* General. (Reserved).
-
- 4.12.2* Window Hardware. (Reserved).
-
- 4.13 Doors.
-
- 4.13.1 General. Doors required to be accessible by 4.1 shall
- comply with the requirements of 4.13.
-
- 4.13.2 Revolving Doors and Turnstiles. Revolving doors or
- turnstiles shall not be the only means of passage at an
- accessible entrance or along an accessible route. An accessible
- gate or door shall be provided adjacent to the turnstile or
- revolving door and shall be so designed as to facilitate the same
- use pattern.
-
- 4.13.3 Gates. Gates, including ticket gates, shall meet all
- applicable specifications of 4.13.
-
- 4.13.4 Double-Leaf Doorways. If doorways have two independently
- operated door leaves, then at least one leaf shall meet the
- specifications in 4.13.5 and 4.13.6. That leaf shall be an
- active leaf.
-
- 4.13.5 Clear Width. Doorways shall have a minimum clear opening
- of 32 in (815 mm) with the door open 90 degrees, measured between
- the face of the door and the opposite stop (see Fig. 24(a), (b),
- (c), and (d)). Openings more than 24 in (610 mm) in depth shall
- comply with 4.2.1 and 4.3.3 (see Fig. 24(e)).
-
- EXCEPTION: Doors not requiring full user passage, such as shallow
- closets, may have the clear opening reduced to 20 in (510 mm)
- minimum.
-
- 4.13.6 Maneuvering Clearances at Doors. Minimum maneuvering
- clearances at doors that are not automatic or power-assisted
- shall be as shown in Fig. 25. The floor or ground area within
- the required clearances shall be level and clear.
-
- EXCEPTION: Entry doors to acute care hospital bedrooms for
- in-patients shall be exempted from the requirement for space at
- the latch side of the door (see dimension "x" in Fig. 25) if the
- door is at least 44 in (1120 mm) wide.
-
- 4.13.7 Two Doors in Series. The minimum space between two hinged
- or pivoted doors in series shall be 48 in (1220 mm) plus the
- width of any door swinging into the space. Doors in series shall
- swing either in the same direction or away from the space between
- the doors (see Fig. 26).
-
- 4.13.8* Thresholds at Doorways. Thresholds at doorways shall not
- exceed 3/4 in (19 mm) in height for exterior sliding doors or 1/2
- in (13 mm) for other types of doors. Raised thresholds and floor
- level changes at accessible doorways shall be beveled with a
- slope no greater than 1:2 (see 4.5.2).
-
- 4.13.9* Door Hardware. Handles, pulls, latches, locks, and other
- operating devices on accessible doors shall have a shape that is
- easy to grasp with one hand and does not require tight grasping,
- tight pinching, or twisting of the wrist to operate.
- Lever-operated mechanisms, push-type mechanisms, and U-shaped
- handles are acceptable designs. When sliding doors are fully
- open, operating hardware shall be exposed and usable from both
- sides. Hardware required for accessible door passage shall be
- mounted no higher than 48 in (1220 mm) above finished floor.
-
- 4.13.10* Door Closers. If a door has a closer, then the sweep
- period of the closer shall be adjusted so that from an open
- position of 70 degrees, the door will take at least 3 seconds to
- move to a point 3 in (75 mm) from the latch, measured to the
- leading edge of the door.
-
- 4.13.11* Door Opening Force. The maximum force for pushing or
- pulling open a door shall be as follows:
-
- (1) Fire doors shall have the minimum opening force
- allowable by the appropriate administrative authority.
-
- (2) Other doors.
-
- (a) exterior hinged doors: (Reserved).
-
- (b) interior hinged doors: 5 lbf (22.2N)
-
- (c) sliding or folding doors: 5 lbf (22.2N)
-
- These forces do not apply to the force required to retract latch
- bolts or disengage other devices that may hold the door in a
- closed position.
-
- 4.13.12* Automatic Doors and Power-Assisted Doors. If an
- automatic door is used, then it shall comply with ANSI/BHMA
- A156.10-1985. Slowly opening, low-powered, automatic doors shall
- comply with ANSI A156.19-1984. Such doors shall not open to back
- check faster than 3 seconds and shall require no more than 15 lbf
- (66.6N) to stop door movement. If a power-assisted door is used,
- its door-opening force shall comply with 4.13.11 and its closing
- shall conform to the requirements in ANSI A156.19-1984.
-
- 4.14 Entrances.
-
- 4.14.1 Minimum Number. Entrances required to be accessible by
- 4.1 shall be part of an accessible route complying with 4.3.
- Such entrances shall be connected by an accessible route to
- public transportation stops, to accessible parking and passenger
- loading zones, and to public streets or sidewalks if available
- (see 4.3.2(1)). They shall also be connected by an accessible
- route to all accessible spaces or elements within the building or
- facility.
-
- 4.14.2 Service Entrances. A service entrance shall not be the
- sole accessible entrance unless it is the only entrance to a
- building or facility (for example, in a factory or garage).
-
- 4.15 Drinking Fountains and Water Coolers.
-
- 4.15.1 Minimum Number. Drinking fountains or water coolers
- required to be accessible by 4.1 shall comply with 4.15.
-
- 4.15.2* Spout Height. Spouts shall be no higher than 36 in (915
- mm), measured from the floor or ground surfaces to the spout
- outlet (see Fig. 27(a)).
-
- 4.15.3 Spout Location. The spouts of drinking fountains and
- water coolers shall be at the front of the unit and shall direct
- the water flow in a trajectory that is parallel or nearly
- parallel to the front of the unit. The spout shall provide a
- flow of water at least 4 in (100 mm) high so as to allow the
- insertion of a cup or glass under the flow of water. On an
- accessible drinking fountain with a round or oval bowl, the spout
- must be positioned so the flow of water is within 3 in (75 mm) of
- the front edge of the fountain.
-
- 4.15.4 Controls. Controls shall comply with 4.27.4. Unit
- controls shall be front mounted or side mounted near the front
- edge.
-
- 4.15.5 Clearances.
-
- (1) Wall- and post-mounted cantilevered units shall have a
- clear knee space between the bottom of the apron and the floor or
- ground at least 27 in (685 mm) high, 30 in (760 mm) wide, and 17
- in to 19 in (430 mm to 485 mm) deep (see Fig. 27(a) and (b)).
- Such units shall also have a minimum clear floor space 30 in by
- 48 in (760 mm by 1220 mm) to allow a person in a wheelchair to
- approach the unit facing forward.
-
- (2) Free-standing or built-in units not having a clear
- space under them shall have a clear floor space at least 30 in by
- 48 in (760 mm by 1220 mm) that allows a person in a wheelchair to
- make a parallel approach to the unit (see Fig. 27(c) and (d)).
- This clear floor space shall comply with 4.2.4.
-
- 4.16 Water Closets.
-
- 4.16.1 General. Accessible water closets shall comply with 4.16.
-
- 4.16.2 Clear Floor Space. Clear floor space for water closets
- not in stalls shall comply with Fig. 28. Clear floor space may
- be arranged to allow either a left-handed or right-handed
- approach.
-
- 4.16.3* Height. The height of water closets shall be 17 in to 19
- in (430 mm to 485 mm), measured to the top of the toilet seat
- (see Fig. 29(b)). Seats shall not be sprung to return to a
- lifted position.
-
- 4.16.4* Grab Bars. Grab bars for water closets not located in
- stalls shall comply with 4.26 and Fig. 29. The grab bar behind
- the water closet shall be 36 in (915 mm) minimum.
-
- 4.16.5* Flush Controls. Flush controls shall be hand operated or
- automatic and shall comply with 4.27.4. Controls for flush
- valves shall be mounted on the wide side of toilet areas no more
- than 44 in (1120 mm) above the floor.
-
- 4.16.6 Dispensers. Toilet paper dispensers shall be installed
- within reach, as shown in Fig. 29(b). Dispensers that control
- delivery, or that do not permit continuous paper flow, shall not
- be used.
-
- 4.17 Toilet Stalls.
-
- 4.17.1 Location. Accessible toilet stalls shall be on an
- accessible route and shall meet the requirements of 4.17.
-
- 4.17.2 Water Closets. Water closets in accessible stalls shall
- comply with 4.16.
-
- 4.17.3* Size and Arrangement. The size and arrangement of the
- standard toilet stall shall comply with Fig. 30(a), Standard
- Stall. Standard toilet stalls with a minimum depth of 56 in
- (1420 mm) (see Fig. 30(a)) shall have wall-mounted water closets.
- If the depth of a standard toilet stall is increased at least 3
- in (75 mm), then a floor-mounted water closet may be used.
- Arrangements shown for standard toilet stalls may be reversed to
- allow either a left- or right-hand approach. Additional stalls
- shall be provided in conformance with 4.22.4.
-
- EXCEPTION: In instances of alteration work where provision of a
- standard stall (Fig. 30(a)) is technically infeasible or where
- plumbing code requirements prevent combining existing stalls to
- provide space, either alternate stall (Fig. 30(b)) may be
- provided in lieu of the standard stall.
-
- 4.17.4 Toe Clearances. In standard stalls, the front partition
- and at least one side partition shall provide a toe clearance of
- at least 9 in (230 mm) above the floor. If the depth of the
- stall is greater than 60 in (1525 mm), then the toe clearance is
- not required.
-
- 4.17.5* Doors. Toilet stall doors, including door hardware,
- shall comply with 4.13. If toilet stall approach is from the
- latch side of the stall door, clearance between the door side of
- the stall and any obstruction may be reduced to a minimum of 42
- in (1065 mm) (Fig. 30).
-
- 4.17.6 Grab Bars. Grab bars complying with the length and
- positioning shown in Fig. 30(a), (b), (c), and (d) shall be
- provided. Grab bars may be mounted with any desired method as
- long as they have a gripping surface at the locations shown and
- do not obstruct the required clear floor area. Grab bars shall
- comply with 4.26.
-
- 4.18 Urinals.
-
- 4.18.1 General. Accessible urinals shall comply with 4.18.
-
- 4.18.2 Height. Urinals shall be stall-type or wall-hung with an
- elongated rim at a maximum of 17 in (430 mm) above the finish
- floor.
-
- 4.18.3 Clear Floor Space. A clear floor space 30 in by 48 in
- (760 mm by 1220 mm) shall be provided in front of urinals to
- allow forward approach. This clear space shall adjoin or overlap
- an accessible route and shall comply with 4.2.4. Urinal shields
- that do not extend beyond the front edge of the urinal rim may be
- provided with 29 in (735 mm) clearance between them.
-
- 4.18.4 Flush Controls. Flush controls shall be hand operated or
- automatic, and shall comply with 4.27.4, and shall be mounted no
- more than 44 in (1120 mm) above the finish floor.
-
- 4.19 Lavatories and Mirrors.
-
- 4.19.1 General. The requirements of 4.19 shall apply to lavatory
- fixtures, vanities, and built-in lavatories.
-
- 4.19.2 Height and Clearances. Lavatories shall be mounted with
- the rim or counter surface no higher than 34 in (865 mm) above
- the finish floor. Provide a clearance of at least 29 in (735 mm)
- above the finish floor to the bottom of the apron. Knee and toe
- clearance shall comply with Fig. 31.
-
- 4.19.3 Clear Floor Space. A clear floor space 30 in by 48 in
- (760 mm by 1220 mm) complying with 4.2.4 shall be provided in
- front of a lavatory to allow forward approach. Such clear floor
- space shall adjoin or overlap an accessible route and shall
- extend a maximum of 19 in (485 mm) underneath the lavatory (see
- Fig. 32).
-
- 4.19.4 Exposed Pipes and Surfaces. Hot water and drain pipes
- under lavatories shall be insulated or otherwise configured to
- protect against contact. There shall be no sharp or abrasive
- surfaces under lavatories.
-
- 4.19.5 Faucets. Faucets shall comply with 4.27.4.
- Lever-operated, push-type, and electronically controlled
- mechanisms are examples of acceptable designs. If self-closing
- valves are used the faucet shall remain open for at least 10
- seconds.
-
- 4.19.6* Mirrors. Mirrors shall be mounted with the bottom edge
- of the reflecting surface no higher than 40 in (1015 mm) above
- the finish floor (see Fig. 31).
-
- 4.20 Bathtubs.
-
- 4.20.1 General. Accessible bathtubs shall comply with 4.20.
-
- 4.20.2 Floor Space. Clear floor space in front of bathtubs shall
- be as shown in Fig. 33.
-
- 4.20.3 Seat. An in-tub seat or a seat at the head end of the tub
- shall be provided as shown in Fig. 33 and 34. The structural
- strength of seats and their attachments shall comply with 4.26.3.
- Seats shall be mounted securely and shall not slip during use.
-
- 4.20.4 Grab Bars. Grab bars complying with 4.26 shall be
- provided as shown in Fig. 33 and 34.
-
- 4.20.5 Controls. Faucets and other controls complying with
- 4.27.4 shall be located as shown in Fig. 34.
-
- 4.20.6 Shower Unit. A shower spray unit with a hose at least 60
- in (1525 mm) long that can be used both as a fixed shower head
- and as a hand-held shower shall be provided.
-
- 4.20.7 Bathtub Enclosures. If provided, enclosures for bathtubs
- shall not obstruct controls or transfer from wheelchairs onto
- bathtub seats or into tubs. Enclosures on bathtubs shall not
- have tracks mounted on their rims.
-
- 4.21 Shower Stalls.
-
- 4.21.1* General. Accessible shower stalls shall comply with
- 4.21.
-
- 4.21.2 Size and Clearances. Except as specified in 9.1.2, shower
- stall size and clear floor space shall comply with Fig. 35(a) or
- (b). The shower stall in Fig. 35(a) shall be 36 in by 36 in (915
- mm by 915 mm). Shower stalls required by 9.1.2 shall comply with
- Fig. 57(a) or (b). The shower stall in Fig. 35(b) will fit into
- the space required for a bathtub.
-
- 4.21.3 Seat. A seat shall be provided in shower stalls 36 in by
- 36 in (915 mm by 915 mm) and shall be as shown in Fig. 36. The
- seat shall be mounted 17 in to 19 in (430 mm to 485 mm) from the
- bathroom floor and shall extend the full depth of the stall. In
- a 36 in by 36 in (915 mm by 915 mm) shower stall, the seat shall
- be on the wall opposite the controls. Where a fixed seat is
- provided in a 30 in by 60 in minimum (760 mm by 1525 mm) shower
- stall, it shall be a folding type and shall be mounted on the
- wall adjacent to the controls as shown in Fig. 57. The
- structural strength of seats and their attachments shall comply
- with 4.26.3.
-
- 4.21.4 Grab Bars. Grab bars complying with 4.26 shall be
- provided as shown in Fig. 37.
-
- 4.21.5 Controls. Faucets and other controls complying with
- 4.27.4 shall be located as shown in Fig. 37. In shower stalls 36
- in by 36 in (915 mm by 915 mm), all controls, faucets, and the
- shower unit shall be mounted on the side wall opposite the seat.
-
- 4.21.6 Shower Unit. A shower spray unit with a hose at least 60
- in (1525 mm) long that can be used both as a fixed shower head
- and as a hand-held shower shall be provided.
-
- EXCEPTION: In unmonitored facilities where vandalism is a
- consideration, a fixed shower head mounted at 48 in (1220 mm)
- above the shower floor may be used in lieu of a hand-held shower
- head.
-
- 4.21.7 Curbs. If provided, curbs in shower stalls 36 in by 36 in
- (915 mm by 915 mm) shall be no higher than 1/2 in (13 mm).
- Shower stalls that are 30 in by 60 in (760 mm by 1525 mm) minimum
- shall not have curbs.
-
- 4.21.8 Shower Enclosures. If provided, enclosures for shower
- stalls shall not obstruct controls or obstruct transfer from
- wheelchairs onto shower seats.
-
- 4.22 Toilet Rooms.
-
- 4.22.1 Minimum Number. Toilet facilities required to be
- accessible by 4.1 shall comply with 4.22. Accessible toilet
- rooms shall be on an accessible route.
-
- 4.22.2 Doors. All doors to accessible toilet rooms shall comply
- with 4.13. Doors shall not swing into the clear floor space
- required for any fixture.
-
- 4.22.3* Clear Floor Space. The accessible fixtures and controls
- required in 4.22.4, 4.22.5, 4.22.6, and 4.22.7 shall be on an
- accessible route. An unobstructed turning space complying with
- 4.2.3 shall be provided within an accessible toilet room. The
- clear floor space at fixtures and controls, the accessible route,
- and the turning space may overlap.
-
- 4.22.4 Water Closets. If toilet stalls are provided, then at
- least one shall be a standard toilet stall complying with 4.17;
- where 6 or more stalls are provided, in addition to the stall
- complying with 4.17.3, at least one stall 36 in (915 mm) wide
- with an outward swinging, self-closing door and parallel grab
- bars complying with Fig. 30(d) and 4.26 shall be provided. Water
- closets in such stalls shall comply with 4.16. If water closets
- are not in stalls, then at least one shall comply with 4.16.
-
- 4.22.5 Urinals. If urinals are provided, then at least one shall
- comply with 4.18.
-
- 4.22.6 Lavatories and Mirrors. If lavatories and mirrors are
- provided, then at least one of each shall comply with 4.19.
-
- 4.22.7 Controls and Dispensers. If controls, dispensers,
- receptacles, or other equipment are provided, then at least one
- of each shall be on an accessible route and shall comply with
- 4.27.
-
- 4.23 Bathrooms, Bathing Facilities, and Shower Rooms.
-
- 4.23.1 Minimum Number. Bathrooms, bathing facilities, or shower
- rooms required to be accessible by 4.1 shall comply with 4.23 and
- shall be on an accessible route.
-
- 4.23.2 Doors. Doors to accessible bathrooms shall comply with
- 4.13. Doors shall not swing into the floor space required for any
- fixture.
-
- 4.23.3* Clear Floor Space. The accessible fixtures and controls
- required in 4.23.4, 4.23.5, 4.23.6, 4.23.7, 4.23.8, and 4.23.9
- shall be on an accessible route. An unobstructed turning space
- complying with 4.2.3 shall be provided within an accessible
- bathroom. The clear floor spaces at fixtures and controls, the
- accessible route, and the turning space may overlap.
-
- 4.23.4 Water Closets. If toilet stalls are provided, then at
- least one shall be a standard toilet stall complying with 4.17;
- where 6 or more stalls are provided, in addition to the stall
- complying with 4.17.3, at least one stall 36 in (915 mm) wide
- with an outward swinging, self-closing door and parallel grab
- bars complying with Fig. 30(d) and 4.26 shall be provided. Water
- closets in such stalls shall comply with 4.16. If water closets
- are not in stalls, then at least one shall comply with 4.16.
-
- 4.23.5 Urinals. If urinals are provided, then at least one shall
- comply with 4.18.
-
- 4.23.6 Lavatories and Mirrors. If lavatories and mirrors are
- provided, then at least one of each shall comply with 4.19.
-
- 4.23.7 Controls and Dispensers. If controls, dispensers,
- receptacles, or other equipment are provided, then at least one
- of each shall be on an accessible route and shall comply with
- 4.27.
-
- 4.23.8 Bathing and Shower Facilities. If tubs or showers are
- provided, then at least one accessible tub that complies with
- 4.20 or at least one accessible shower that complies with 4.21
- shall be provided.
-
- 4.23.9* Medicine Cabinets. If medicine cabinets are provided, at
- least one shall be located with a usable shelf no higher than 44
- in (1120 mm) above the floor space. The floor space shall comply
- with 4.2.4.
-
- 4.24 Sinks.
-
- 4.24.1 General. Sinks required to be accessible by 4.1 shall
- comply with 4.24.
-
- 4.24.2 Height. Sinks shall be mounted with the counter or rim no
- higher than 34 in (865 mm) above the finish floor.
-
- 4.24.3 Knee Clearance. Knee clearance that is at least 27 in
- (685 mm) high, 30 in (760 mm) wide, and 19 in (485 mm) deep shall
- be provided underneath sinks.
-
- 4.24.4 Depth. Each sink shall be a maximum of 6-1/2 in (165 mm)
- deep.
-
- 4.24.5 Clear Floor Space. A clear floor space at least 30 in by
- 48 in (760 mm by 1220 mm) complying with 4.2.4 shall be provided
- in front of a sink to allow forward approach. The clear floor
- space shall be on an accessible route and shall extend a maximum
- of 19 in (485 mm) underneath the sink (see Fig. 32).
-
- 4.24.6 Exposed Pipes and Surfaces. Hot water and drain pipes
- exposed under sinks shall be insulated or otherwise configured so
- as to protect against contact. There shall be no sharp or
- abrasive surfaces under sinks.
-
- 4.24.7 Faucets. Faucets shall comply with 4.27.4.
- Lever-operated, push-type, touch-type, or electronically
- controlled mechanisms are acceptable designs.
-
- 4.25 Storage.
-
- 4.25.1 General. Fixed storage facilities such as cabinets,
- shelves, closets, and drawers required to be accessible by 4.1
- shall comply with 4.25.
-
- 4.25.2 Clear Floor Space. A clear floor space at least 30 in by
- 48 in (760 mm by 1220 mm) complying with 4.2.4 that allows either
- a forward or parallel approach by a person using a wheelchair
- shall be provided at accessible storage facilities.
-
- 4.25.3 Height. Accessible storage spaces shall be within at
- least one of the reach ranges specified in 4.2.5 and 4.2.6 (see
- Fig. 5 and Fig 6). Clothes rods or shelves shall be a maximum of
- 54 in (1370 mm) above the finish floor for a side approach.
- Where the distance from the wheelchair to the clothes rod or
- shelf exceeds 10 in (255 mm) (as in closets without accessible
- doors) the height and depth to the rod or shelf shall comply with
- Fig. 38(a) and Fig. 38(b).
-
- 4.25.4 Hardware. Hardware for accessible storage facilities
- shall comply with 4.27.4. Touch latches and U-shaped pulls are
- acceptable.
-
- 4.26 Handrails, Grab Bars, and Tub and Shower Seats.
-
- 4.26.1* General. All handrails, grab bars, and tub and shower
- seats required to be accessible by 4.1, 4.8, 4.9, 4.16, 4.17,
- 4.20 or 4.21 shall comply with 4.26.
-
- 4.26.2* Size and Spacing of Grab Bars and Handrails. The
- diameter or width of the gripping surfaces of a handrail or grab
- bar shall be 1-1/4 in to 1-1/2 in (32 mm to 38 mm), or the shape
- shall provide an equivalent gripping surface. If handrails or
- grab bars are mounted adjacent to a wall, the space between the
- wall and the grab bar shall be 1-1/2 in (38 mm) (see Fig. 39(a),
- (b), (c), and (e)). Handrails may be located in a recess if the
- recess is a maximum of 3 in (75 mm) deep and extends at least 18
- in (455 mm) above the top of the rail (see Fig. 39(d)).
-
- 4.26.3 Structural Strength. The structural strength of grab
- bars, tub and shower seats, fasteners, and mounting devices shall
- meet the following specification:
-