home *** CD-ROM | disk | FTP | other *** search
/ Complete Home & Office Legal Guide / Complete Home and Office Legal Guide (Chestnut) (1993).ISO / stat / eeoc / build2.asc < prev    next >
Encoding:
Text File  |  1993-08-26  |  58.1 KB  |  1,306 lines

  1. /* Part 2 of 4 of the builidng requirments follows. */
  2. 4.1.7 Accessible Buildings: Historic Preservation.
  3.  
  4.  (1) Applicability:
  5.  
  6.  (a) General Rule.  Alterations to a qualified historic 
  7. building or facility shall comply with 4.1.6 Accessible 
  8. Buildings:  Alterations, the applicable technical specifications 
  9. of 4.2 through 4.35 and the applicable special application 
  10. sections 5 through 10 unless it is determined in accordance with 
  11. the procedures in 4.1.7(2) that compliance with the requirements 
  12. for accessible routes (exterior and interior), ramps, entrances, 
  13. or toilets would threaten or destroy the historic significance of 
  14. the building or facility in which case the alternative 
  15. requirements in 4.1.7(3) may be used for the feature.
  16.  
  17.  EXCEPTION:  (Reserved).
  18.  
  19.  (b) Definition.  A qualified historic building or facility 
  20. is a building or facility that is:
  21.  
  22.  (i) Listed in or eligible for listing in the National 
  23. Register of Historic Places; or
  24.  
  25.  (ii) Designated as historic under an appropriate State or 
  26. local law.
  27.  
  28.  (2) Procedures:
  29.  
  30.  (a) Alterations to Qualified Historic Buildings and 
  31.                            
  32. Facilities Subject to Section 106 of the National Historic 
  33. Preservation Act:
  34.  
  35.  (i) Section 106 Process.  Section 106 of the National 
  36. Historic Preservation Act (16 U.S.C. 470 f) requires that a 
  37. Federal agency with jurisdiction over a Federal, federally 
  38. assisted, or federally licensed undertaking consider the effects 
  39. of the agency's undertaking on buildings and facilities listed in 
  40. or eligible for listing in the National Register of Historic 
  41. Places and give the Advisory Council on Historic Preservation a 
  42. reasonable opportunity to comment on the undertaking prior to 
  43. approval of the undertaking.
  44.  
  45.  (ii) ADA Application.  Where alterations are undertaken 
  46. to a qualified historic building or facility that is subject to 
  47. section 106 of the National Historic Preservation Act, the 
  48. Federal agency with jurisdiction over the undertaking shall 
  49. follow the section 106 process.  If the State Historic 
  50. Preservation Officer or Advisory Council on Historic Preservation 
  51. agrees that compliance with the requirements for accessible 
  52. routes (exterior and interior), ramps, entrances, or toilets 
  53. would threaten or destroy the historic significance of the 
  54. building or facility, the alternative requirements in 4.1.7(3) 
  55. may be used for the feature.
  56.  
  57.  (b) Alterations to Qualified Historic Buildings and 
  58. Facilities Not Subject to Section 106 of the National Historic 
  59. Preservation Act.  Where alterations are undertaken to a 
  60. qualified historic building or facility that is not subject to 
  61. section 106 of the National Historic Preservation Act, if the 
  62. entity undertaking the alterations believes that compliance with 
  63. the requirements for accessible routes (exterior and interior), 
  64. ramps, entrances, or toilets would threaten or destroy the 
  65. historic significance of the building or facility and that the 
  66. alternative requirements in 4.1.7(3) should be used for the 
  67. feature, the entity should consult with the State Historic 
  68. Preservation Officer.  If the State Historic Preservation Officer 
  69. agrees that compliance with the accessibility requirements for 
  70. accessible routes (exterior and interior), ramps, entrances or 
  71. toilets would threaten or destroy the historical significance of 
  72. the building or facility, the alternative requirements in 
  73. 4.1.7(3) may be used.
  74.  
  75.  (c) Consultation With Interested Persons.  Interested 
  76. persons should be invited to participate in the consultation 
  77. process, including State or local accessibility officials, 
  78. individuals with disabilities, and organizations representing 
  79. individuals with disabilities.
  80.  
  81.  (d) Certified Local Government Historic Preservation 
  82. Programs.  Where the State Historic Preservation Officer has 
  83. delegated the consultation responsibility for purposes of this 
  84. section to a local government historic preservation program that 
  85. has been certified in accordance with section 101(c) of the 
  86. National Historic Preservation Act of 1966 (16 U.S.C. 470a (c)) 
  87. and implementing regulations (36 CFR 61.5), the responsibility 
  88. may be carried out by the appropriate local government body or 
  89. official.
  90.  
  91.  (3) Historic Preservation: Minimum Requirements:
  92.  
  93.  (a) At least one accessible route complying with 4.3 from 
  94. a site access point to an accessible entrance shall be provided.
  95.  
  96. EXCEPTION: A ramp with a slope no greater than 1:6 for a run not 
  97. to exceed 2 ft (610 mm) may be used as part of an accessible 
  98. route to an entrance.
  99.  
  100.  (b) At least one accessible entrance complying with 4.14 
  101. which is used by the public shall be provided.
  102.  
  103. EXCEPTION: If it is determined that no entrance used by the 
  104. public can comply with 4.14, then access at any entrance not used 
  105. by the general public but open (unlocked) with directional 
  106. signage at the primary entrance may be used.  The accessible 
  107. entrance shall also have a notification system.  Where security 
  108. is a problem, remote monitoring may be used.
  109.  
  110.  (c) If toilets are provided, then at least one toilet 
  111. facility complying with 4.22 and 4.1.6 shall be provided along an 
  112. accessible route that complies with 4.3.  Such toilet facility 
  113. may be unisex in design.
  114.  
  115.  (d) Accessible routes from an accessible entrance to all 
  116. publicly used spaces on at least the level of the accessible 
  117. entrance shall be provided.  Access shall be provided to all 
  118. levels of a building or facility in compliance with 4.1 whenever 
  119. practical.
  120.  
  121.  (e) Displays and written information, documents, etc., 
  122. should be located where they can be seen by a seated person.  
  123. Exhibits and signage displayed horizontally (e.g., open books), 
  124. should be no higher than 44 in (1120 mm) above the floor surface.
  125.  
  126. NOTE: The technical provisions of sections 4.2 through 4.35 are 
  127. the same as those of the American National Standard Institute's 
  128. document A117.1-1980, except as noted in the text.
  129.  
  130. 4.2 Space Allowance and Reach Ranges.
  131.  
  132. 4.2.1* Wheelchair Passage Width.  The minimum clear width for 
  133. single wheelchair passage shall be 32 in (815 mm) at a point and 
  134. 36 in (915 mm) continuously (see Fig. 1 and 24(e)).
  135.  
  136. 4.2.2 Width for Wheelchair Passing.  The minimum width for two 
  137. wheelchairs to pass is 60 in (1525 mm) (see Fig. 2).
  138.  
  139. 4.2.3* Wheelchair Turning Space.  The space required for a 
  140. wheelchair to make a 180-degree turn is a clear space of 60 in 
  141. (1525 mm) diameter (see Fig. 3(a)) or a T-shaped space (see Fig.  
  142. 3(b)).
  143.  
  144. 4.2.4* Clear Floor or Ground Space for Wheelchairs.
  145.  
  146. 4.2.4.1 Size and Approach.  The minimum clear floor or ground 
  147. space required to accommodate a single, stationary wheelchair and 
  148. occupant is 30 in by 48 in (760 mm by 1220 mm) (see Fig. 4(a)).  
  149. The minimum clear floor or ground space for wheelchairs may be 
  150. positioned for forward or parallel approach to an object (see 
  151. Fig.  4(b) and (c)).  Clear floor or ground space for wheelchairs 
  152. may be part of the knee space required under some objects.
  153.  
  154. 4.2.4.2 Relationship of Maneuvering Clearance to Wheelchair 
  155. Spaces.  One full unobstructed side of the clear floor or ground 
  156. space for a wheelchair shall adjoin or overlap an accessible 
  157. route or adjoin another wheelchair clear floor space.  If a clear 
  158. floor space is located in an alcove or otherwise confined on all 
  159. or part of three sides, additional maneuvering clearances shall 
  160. be provided as shown in Fig. 4(d) and (e).
  161.  
  162. 4.2.4.3 Surfaces for Wheelchair Spaces.  Clear floor or ground 
  163. spaces for wheelchairs shall comply with 4.5.
  164.  
  165. 4.2.5* Forward Reach.  If the clear floor space only allows 
  166. forward approach to an object, the maximum high forward reach 
  167. allowed shall be 48 in (1220 mm) (see Fig. 5(a)).  The minimum 
  168. low forward reach is 15 in (380 mm).  If the high forward reach 
  169. is over an obstruction, reach and clearances shall be as shown in 
  170. Fig. 5(b).
  171.  
  172. 4.2.6* Side Reach.  If the clear floor space allows parallel 
  173. approach by a person in a wheelchair, the maximum high side reach 
  174. allowed shall be 54 in (1370 mm) and the low side reach shall be 
  175. no less than 9 in (230 mm) above the floor (Fig. 6(a) and (b)).  
  176. If the side reach is over an obstruction, the reach and 
  177. clearances shall be as shown in Fig 6(c).
  178.  
  179. 4.3 Accessible Route.
  180.  
  181. 4.3.1* General.  All walks, halls, corridors, aisles, skywalks, 
  182. tunnels, and other spaces that are part of an accessible route 
  183. shall comply with 4.3.
  184.  
  185. 4.3.2 Location.
  186.  
  187.  (1) At least one accessible route within the boundary of 
  188. the site shall be provided from public transportation stops, 
  189. accessible parking, and accessible passenger loading zones, and 
  190. public streets or sidewalks to the accessible building entrance 
  191. they serve.  The accessible route shall, to the maximum extent 
  192. feasible, coincide with the route for the general public.
  193.  
  194.  (2) At least one accessible route shall connect accessible 
  195. buildings, facilities, elements, and spaces that are on the same 
  196. site.
  197.  
  198.  (3) At least one accessible route shall connect accessible 
  199. building or facility entrances with all accessible spaces and 
  200. elements and with all accessible dwelling units within the 
  201. building or facility.
  202.  
  203.  (4) An accessible route shall connect at least one 
  204. accessible entrance of each accessible dwelling unit with those 
  205. exterior and interior spaces and facilities that serve the 
  206. accessible dwelling unit.
  207.  
  208. 4.3.3 Width.  The minimum clear width of an accessible route 
  209. shall be 36 in (915 mm) except at doors (see 4.13.5 and 4.13.6).  
  210. If a person in a wheelchair must make a turn around an 
  211. obstruction, the minimum clear width of the accessible route 
  212. shall be as shown in Fig. 7(a) and (b).
  213.  
  214. 4.3.4 Passing Space.  If an accessible route has less than 60 in 
  215. (1525 mm) clear width, then passing spaces at least 60 in by 60 
  216. in (1525 mm by 1525 mm) shall be located at reasonable intervals 
  217. not to exceed 200 ft (61 m).  A T-intersection of two corridors 
  218. or walks is an acceptable passing place.
  219.  
  220. 4.3.5 Head Room.  Accessible routes shall comply with 4.4.2.
  221.  
  222. 4.3.6 Surface Textures.  The surface of an accessible route shall 
  223. comply with 4.5.
  224.  
  225. 4.3.7 Slope.  An accessible route with a running slope greater 
  226. than 1:20 is a ramp and shall comply with 4.8.  Nowhere shall the 
  227. cross slope of an accessible route exceed 1:50.
  228.  
  229. 4.3.8 Changes in Levels.  Changes in levels along an accessible 
  230. route shall comply with 4.5.2.  If an accessible route has 
  231. changes in level greater than 1/2 in (13 mm), then a curb ramp, 
  232. ramp, elevator, or platform lift (as permitted in 4.1.3 and 
  233. 4.1.6) shall be provided that complies with 4.7, 4.8, 4.10, or 
  234. 4.11, respectively.  An accessible route does not include stairs, 
  235. steps, or escalators.  See definition of "egress, means of" in 
  236. 3.5.
  237.  
  238. 4.3.9 Doors.  Doors along an accessible route shall comply with 
  239. 4.13.
  240.  
  241. 4.3.10* Egress.  Accessible routes serving any accessible space 
  242. or element shall also serve as a means of egress for emergencies 
  243. or connect to an accessible area of rescue assistance.
  244.  
  245. 4.3.11 Areas of Rescue Assistance.
  246.  
  247. 4.3.11.1 Location and Construction.  An area of rescue assistance 
  248. shall be one of the following:
  249.  
  250.  (1) A portion of a stairway landing within a smokeproof 
  251. enclosure (complying with local requirements).
  252.  
  253.  (2) A portion of an exterior exit balcony located 
  254. immediately adjacent to an exit stairway when the balcony 
  255. complies with local requirements for exterior exit balconies.  
  256. Openings to the interior of the building located within 20 feet 
  257. (6 m) of the area of rescue assistance shall be protected with 
  258. fire assemblies having a three- fourths hour fire protection 
  259. rating.
  260.  
  261.  (3) A portion of a one-hour fire-resistive corridor 
  262. (complying with local requirements for fire-resistive 
  263. construction and for openings) located immediately adjacent to an 
  264. exit enclosure.
  265.  
  266.  (4) A vestibule located immediately adjacent to an exit 
  267. enclosure and constructed to the same fire-resistive standards as 
  268. required for corridors and openings.
  269.  
  270.  (5) A portion of a stairway landing within an exit 
  271. enclosure which is vented to the exterior and is separated from 
  272. the interior of the building with not less than one-hour 
  273. fire-resistive doors.
  274.  
  275.  (6) When approved by the appropriate local authority, an 
  276. area or a room which is separated from other portions of the 
  277. building by a smoke barrier.  Smoke barriers shall have a 
  278. fire-resistive rating of not less than one hour and shall 
  279. completely enclose the area or room.  Doors in the smoke barrier 
  280. shall be tight-fitting smoke- and draft-control assemblies having 
  281. a fire-protection rating of not less than 20 minutes and shall be 
  282. self-closing or automatic closing.  The area or room shall be 
  283. provided with an exit directly to an exit enclosure.  Where the 
  284. room or area exits into an exit enclosure which is required to be 
  285. of more than one-hour fire- resistive construction, the room or 
  286. area shall have the same fire- resistive construction, including 
  287. the same opening protection, as required for the adjacent exit 
  288. enclosure.
  289.  
  290.  (7) An elevator lobby when elevator shafts and adjacent 
  291. lobbies are pressurized as required for smokeproof enclosures by 
  292. local regulations and when complying with requirements herein for 
  293. size, communication, and signage.  Such pressurization system 
  294. shall be activated by smoke detectors on each floor located in a 
  295. manner approved by the appropriate local authority.  
  296. Pressurization equipment and its duct work within the building 
  297. shall be separated from other portions of the building by a 
  298. minimum two-hour fire- resistive construction.
  299.  
  300. 4.3.11.2 Size.  Each area of rescue assistance shall provide at 
  301. least two accessible areas each being not less than 30 inches by 
  302. 48 inches (760 mm by 1220 mm).  The area of rescue assistance 
  303. shall not encroach on any required exit width.  The total number 
  304. of such 30-inch by 48-inch (760 mm by 1220 mm) areas per story 
  305. shall be not less than one for every 200 persons of calculated 
  306. occupant load served by the area of rescue assistance.
  307.  
  308. EXCEPTION: The appropriate local authority may reduce the minimum 
  309. number of 30-inch by 48-inch (760 mm by 1220 mm) areas to one for 
  310. each area of rescue assistance on floors where the occupant load 
  311. is less than 200.
  312.  
  313. 4.3.11.3* Stairway Width.  Each stairway adjacent to an area of 
  314. rescue assistance shall have a minimum clear width of 48 inches 
  315. between handrails.
  316.  
  317. 4.3.11.4* Two-way Communication.  A method of two-way 
  318. communication, with both visible and audible signals, shall be 
  319. provided between each area of rescue assistance and the primary 
  320. entry.  The fire department or appropriate local authority may 
  321. approve a location other than the primary entry.
  322.  
  323. 4.3.11.5 Identification.  Each area of rescue assistance shall be 
  324. identified by a sign which states "AREA OF RESCUE ASSISTANCE" and 
  325. displays the international symbol of accessibility.  The sign 
  326. shall be illuminated when exit sign illumination is required.  
  327. Signage shall also be installed at all inaccessible exits and 
  328. where otherwise necessary to clearly indicate the direction to 
  329. areas of rescue assistance.  In each area of rescue assistance, 
  330. instructions on the use of the area under emergency conditions 
  331. shall be posted adjoining the two-way communication system.
  332.  
  333. 4.4 Protruding Objects.
  334.  
  335. 4.4.1* General.  Objects projecting from walls (for example, 
  336. telephones) with their leading edges between 27 in and 80 in (685 
  337. mm and 2030 mm) above the finished floor shall protrude no more 
  338. than 4 in (100 mm) into walks, halls, corridors, passageways, or 
  339. aisles (see Fig. 8(a)).  Objects mounted with their leading edges 
  340. at or below 27 in (685 mm) above the finished floor may protrude 
  341. any amount (see Fig. 8(a) and (b)).  Free-standing objects 
  342. mounted on posts or pylons may overhang 12 in (305 mm) maximum 
  343. from 27 in to 80 in (685 mm to 2030 mm) above the ground or 
  344. finished floor (see Fig. 8(c) and (d)).  Protruding objects shall 
  345. not reduce the clear width of an accessible route or maneuvering 
  346. space (see Fig.  8(e)).
  347.  
  348. 4.4.2 Head Room.  Walks, halls, corridors, passageways, aisles, 
  349. or other circulation spaces shall have 80 in (2030 mm) minimum 
  350. clear head room (see Fig. 8(a)).  If vertical clearance of an 
  351. area adjoining an accessible route is reduced to less than 80 in 
  352. (nominal dimension), a barrier to warn blind or visually-impaired 
  353. persons shall be provided (see Fig. 8(c-1)).
  354.  
  355. 4.5 Ground and Floor Surfaces.
  356.  
  357. 4.5.1* General.  Ground and floor surfaces along accessible 
  358. routes and in accessible rooms and spaces including floors, 
  359. walks, ramps, stairs, and curb ramps, shall be stable, firm, 
  360. slip-resistant, and shall comply with 4.5.
  361.  
  362. 4.5.2 Changes in Level.  Changes in level up to 1/4 in (6 mm) may 
  363. be vertical and without edge treatment (see Fig. 7(c) ).  Changes 
  364. in level between 1/4 in and 1/2 in (6 mm and 13 mm) shall be 
  365. beveled with a slope no greater than 1:2 (see Fig. 7(d) ).  
  366. Changes in level greater than 1/2 in (13 mm) shall be 
  367. accomplished by means of a ramp that complies with 4.7 or 4.8.
  368.  
  369. 4.5.3* Carpet.  If carpet or carpet tile is used on a ground or 
  370. floor surface, then it shall be securely attached; have a firm 
  371. cushion, pad, or backing, or no cushion or pad; and have a level 
  372. loop, textured loop, level cut pile, or level cut/uncut pile 
  373. texture.  The maximum pile thickness shall be 1/2 in (13 mm) (see 
  374. Fig. 8(f)).  Exposed edges of carpet shall be fastened to floor 
  375. surfaces and have trim along the entire length of the exposed 
  376. edge.  Carpet edge trim shall comply with 4.5.2.
  377.  
  378. 4.5.4 Gratings.  If gratings are located in walking surfaces, 
  379. then they shall have spaces no greater than 1/2 in (13 mm) wide 
  380. in one direction (see Fig. 8(g)).  If gratings have elongated 
  381. openings, then they shall be placed so that the long dimension is 
  382. perpendicular to the dominant direction of travel (see Fig. 
  383. 8(h)).
  384.  
  385. 4.6 Parking and Passenger Loading Zones.
  386.  
  387. 4.6.1 Minimum Number.  Parking spaces required to be accessible 
  388. by 4.1 shall comply with 4.6.2 through 4.6.5.  Passenger loading 
  389. zones required to be accessible by 4.1 shall comply with 4.6.5 
  390. and 4.6.6.
  391.  
  392. 4.6.2 Location.  Accessible parking spaces serving a particular 
  393. building shall be located on the shortest accessible route of 
  394. travel from adjacent parking to an accessible entrance.  In 
  395. parking facilities that do not serve a particular building, 
  396. accessible parking shall be located on the shortest accessible 
  397. route of travel to an accessible pedestrian entrance of the 
  398. parking facility.  In buildings with multiple accessible 
  399. entrances with adjacent parking, accessible parking spaces shall 
  400. be dispersed and located closest to the accessible entrances.
  401.  
  402. 4.6.3* Parking Spaces.  Accessible parking spaces shall be at 
  403. least 96 in (2440 mm) wide.  Parking access aisles shall be part 
  404. of an accessible route to the building or facility entrance and 
  405. shall comply with 4.3.  Two accessible parking spaces may share a 
  406. common access aisle (see Fig. 9).  Parked vehicle overhangs shall 
  407. not reduce the clear width of an accessible route.  Parking 
  408. spaces and access aisles shall be level with surface slopes not 
  409. exceeding 1:50 (2%) in all directions.
  410.  
  411. 4.6.4* Signage.  Accessible parking spaces shall be designated as 
  412. reserved by a sign showing the symbol of accessibility (see 
  413. 4.30.7).  Spaces complying with 4.1.2(5)(b) shall have an 
  414. additional sign "Van-Accessible" mounted below the symbol of 
  415. accessibility.  Such signs shall be located so they cannot be 
  416. obscured by a vehicle parked in the space.
  417.  
  418. 4.6.5* Vertical Clearance.  Provide minimum vertical clearance of 
  419. 114 in (2895 mm) at accessible passenger loading zones and along 
  420. at least one vehicle access route to such areas from site 
  421. entrance(s) and exit(s).  At parking spaces complying with 
  422. 4.1.2(5)(b), provide minimum vertical clearance of 98 in (2490 
  423. mm) at the parking space and along at least one vehicle access 
  424. route to such spaces from site entrance(s) and exit(s).
  425.  
  426. 4.6.6 Passenger Loading Zones.  Passenger loading zones shall 
  427. provide an access aisle at least 60 in (1525 mm) wide and 20 ft 
  428. (240 in)(6100 mm) long adjacent and parallel to the vehicle 
  429. pull-up space (see Fig. 10).  If there are curbs between the 
  430. access aisle and the vehicle pull-up space, then a curb ramp 
  431. complying with 4.7 shall be provided.  Vehicle standing spaces 
  432. and access aisles shall be level with surface slopes not 
  433. exceeding 1:50 (2%) in all directions.
  434.  
  435. 4.7 Curb Ramps.
  436.  
  437. 4.7.1 Location.  Curb ramps complying with 4.7 shall be provided 
  438. wherever an accessible route crosses a curb.
  439.  
  440. 4.7.2 Slope.  Slopes of curb ramps shall comply with 4.8.2.  The 
  441. slope shall be measured as shown in Fig. 11.  Transitions from 
  442. ramps to walks, gutters, or streets shall be flush and free of 
  443. abrupt changes.  Maximum slopes of adjoining gutters, road 
  444. surface immediately adjacent to the curb ramp, or accessible 
  445. route shall not exceed 1:20.
  446.  
  447. 4.7.3 Width.  The minimum width of a curb ramp shall be 36 in 
  448. (915 mm), exclusive of flared sides.
  449.  
  450. 4.7.4 Surface.  Surfaces of curb ramps shall comply with 4.5.
  451.  
  452. 4.7.5 Sides of Curb Ramps.  If a curb ramp is located where 
  453. pedestrians must walk across the ramp, or where it is not 
  454. protected by handrails or guardrails, it shall have flared sides; 
  455. the maximum slope of the flare shall be 1:10 (see Fig. 12(a)).  
  456. Curb ramps with returned curbs may be used where pedestrians 
  457. would not normally walk across the ramp (see Fig. 12(b)).
  458.  
  459. 4.7.6 Built-up Curb Ramps.  Built-up curb ramps shall be located 
  460. so that they do not project into vehicular traffic lanes (see 
  461. Fig.  13).
  462.  
  463. 4.7.7 Detectable Warnings.  A curb ramp shall have a detectable 
  464. warning complying with 4.29.2.  The detectable warning shall 
  465. extend the full width and depth of the curb ramp.
  466.  
  467. 4.7.8 Obstructions.  Curb ramps shall be located or protected to 
  468. prevent their obstruction by parked vehicles.
  469.  
  470. 4.7.9 Location at Marked Crossings.  Curb ramps at marked 
  471. crossings shall be wholly contained within the markings, 
  472. excluding any flared sides (see Fig. 15).
  473.  
  474. 4.7.10 Diagonal Curb Ramps.  If diagonal (or corner type) curb 
  475. ramps have returned curbs or other well-defined edges, such edges 
  476. shall be parallel to the direction of pedestrian flow.  The 
  477. bottom of diagonal curb ramps shall have 48 in (1220 mm) minimum 
  478. clear space as shown in Fig. 15(c) and (d).  If diagonal curb 
  479. ramps are provided at marked crossings, the 48 in (1220 mm) clear 
  480. space shall be within the markings (see Fig. 15(c) and (d)).  If 
  481. diagonal curb ramps have flared sides, they shall also have at 
  482. least a 24 in (610 mm) long segment of straight curb located on 
  483. each side of the curb ramp and within the marked crossing (see 
  484. Fig. 15(c)).
  485.  
  486. 4.7.11 Islands.  Any raised islands in crossings shall be cut 
  487. through level with the street or have curb ramps at both sides 
  488. and a level area at least 48 in (1220 mm) long between the curb 
  489. ramps in the part of the island intersected by the crossings (see 
  490. Fig.  15(a) and (b)).
  491.  
  492. 4.8 Ramps.
  493.  
  494. 4.8.1* General.  Any part of an accessible route with a slope 
  495. greater than 1:20 shall be considered a ramp and shall comply 
  496. with 4.8.
  497.  
  498. 4.8.2* Slope and Rise.  The least possible slope shall be used 
  499. for any ramp.  The maximum slope of a ramp in new construction 
  500. shall be 1:12.  The maximum rise for any run shall be 30 in (760 
  501. mm) (see Fig. 16).  Curb ramps and ramps to be constructed on 
  502. existing sites or in existing buildings or facilities may have 
  503. slopes and rises as allowed in 4.1.6(3)(a) if space limitations 
  504. prohibit the use of a 1:12 slope or less.
  505.  
  506. 4.8.3 Clear Width.  The minimum clear width of a ramp shall be 36 
  507. in (915 mm).
  508.  
  509. 4.8.4* Landings.  Ramps shall have level landings at bottom and 
  510. top of each ramp and each ramp run.  Landings shall have the 
  511. following features:
  512.  
  513.  (1) The landing shall be at least as wide as the ramp run 
  514. leading to it.
  515.  
  516.  (2) The landing length shall be a minimum of 60 in (1525 
  517. mm) clear.
  518.  
  519.  (3) If ramps change direction at landings, the minimum 
  520. landing size shall be 60 in by 60 in (1525 mm by 1525 mm).
  521.  
  522.  (4) If a doorway is located at a landing, then the area in 
  523. front of the doorway shall comply with 4.13.6.
  524.  
  525. 4.8.5* Handrails.  If a ramp run has a rise greater than 6 in 
  526. (150 mm) or a horizontal projection greater than 72 in (1830 mm), 
  527. then it shall have handrails on both sides.  Handrails are not 
  528. required on curb ramps or adjacent to seating in assembly areas.  
  529. Handrails shall comply with 4.26 and shall have the following 
  530. features:
  531.  
  532.  (1) Handrails shall be provided along both sides of ramp 
  533. segments.  The inside handrail on switchback or dogleg ramps 
  534. shall always be continuous.
  535.  
  536.  (2) If handrails are not continuous, they shall extend at 
  537. least 12 in (305 mm) beyond the top and bottom of the ramp 
  538. segment and shall be parallel with the floor or ground surface 
  539. (see Fig. 17).
  540.  
  541.  (3) The clear space between the handrail and the wall 
  542. shall be 1
  543. - 1/2 in (38 mm).
  544.  
  545.  (4) Gripping surfaces shall be continuous.
  546.  
  547.  (5) Top of handrail gripping surfaces shall be mounted 
  548. between 34 in and 38 in (865 mm and 965 mm) above ramp surfaces.
  549.  
  550.  (6) Ends of handrails shall be either rounded or returned 
  551. smoothly to floor, wall, or post.
  552.  
  553.  (7) Handrails shall not rotate within their fittings.
  554.  
  555. 4.8.6 Cross Slope and Surfaces.  The cross slope of ramp surfaces 
  556. shall be no greater than 1:50.  Ramp surfaces shall comply with 
  557. 4.5.
  558.  
  559. 4.8.7 Edge Protection.  Ramps and landings with drop-offs shall 
  560. have curbs, walls, railings, or projecting surfaces that prevent 
  561. people from slipping off the ramp.  Curbs shall be a minimum of 2 
  562. in (50 mm) high (see Fig. 17).
  563.  
  564. 4.8.8 Outdoor Conditions.  Outdoor ramps and their approaches 
  565. shall be designed so that water will not accumulate on walking 
  566. surfaces.
  567.  
  568. 4.9 Stairs.
  569.  
  570. 4.9.1* Minimum Number.  Stairs required to be accessible by 4.1 
  571. shall comply with 4.9.
  572.  
  573. 4.9.2 Treads and Risers.  On any given flight of stairs, all 
  574. steps shall have uniform riser heights and uniform tread widths.  
  575. Stair treads shall be no less than 11 in (280 mm) wide, measured 
  576. from riser to riser (see Fig. 18(a)).  Open risers are not 
  577. permitted.
  578.  
  579. 4.9.3 Nosings.  The undersides of nosings shall not be abrupt.  
  580. The radius of curvature at the leading edge of the tread shall be 
  581. no greater than 1/2 in (13 mm).  Risers shall be sloped or the 
  582. underside of the nosing shall have an angle not less than 60 
  583. degrees from the horizontal.  Nosings shall project no more than 
  584. 1-1/2 in (38 mm) (see Fig. 18).
  585.  
  586. 4.9.4 Handrails.  Stairways shall have handrails at both sides of 
  587. all stairs.  Handrails shall comply with 4.26 and shall have the 
  588. following features:
  589.  
  590.  (1) Handrails shall be continuous along both sides of 
  591. stairs.  The inside handrail on switchback or dogleg stairs shall 
  592. always be continuous (see Fig. 19(a) and (b)).
  593.  
  594.  (2) If handrails are not continuous, they shall extend at 
  595. least 12 in (305 mm) beyond the top riser and at least 12 in (305 
  596. mm) plus the width of one tread beyond the bottom riser.  At the 
  597. top, the extension shall be parallel with the floor or ground 
  598. surface.  At the bottom, the handrail shall continue to slope for 
  599. a distance of the width of one tread from the bottom riser; the 
  600. remainder of the extension shall be horizontal (see Fig. 19(c) 
  601. and (d)).  Handrail extensions shall comply with 4.4.
  602.  
  603.  (3) The clear space between handrails and wall shall be 
  604. 1-1/2 in (38 mm).
  605.  
  606.  (4) Gripping surfaces shall be uninterrupted by newel 
  607. posts, other construction elements, or obstructions.
  608.  
  609.  (5) Top of handrail gripping surface shall be mounted 
  610. between 34 in and 38 in (865 mm and 965 mm) above stair nosings.
  611.  
  612.  (6) Ends of handrails shall be either rounded or returned 
  613. smoothly to floor, wall or post.
  614.  
  615.  (7) Handrails shall not rotate within their fittings.
  616.  
  617. 4.9.5 Detectable Warnings at Stairs.  (Reserved).
  618.  
  619. 4.9.6 Outdoor Conditions.  Outdoor stairs and their approaches 
  620. shall be designed so that water will not accumulate on walking 
  621. surfaces.
  622.  
  623. 4.10 Elevators.
  624.  
  625. 4.10.1 General.  Accessible elevators shall be on an accessible 
  626. route and shall comply with 4.10 and with the ASME A17.1-1990, 
  627. Safety Code for Elevators and Escalators.  Freight elevators 
  628. shall not be considered as meeting the requirements of this 
  629. section unless the only elevators provided are used as 
  630. combination passenger and freight elevators for the public and 
  631. employees.
  632.  
  633. 4.10.2 Automatic Operation.  Elevator operation shall be 
  634. automatic.  Each car shall be equipped with a self-leveling 
  635. feature that will automatically bring the car to floor landings 
  636. within a tolerance of 1/2 in (13 mm) under rated loading to zero 
  637. loading conditions.  This self-leveling feature shall be 
  638. automatic and independent of the operating device and shall 
  639. correct the overtravel or undertravel.
  640.  
  641. 4.10.3 Hall Call Buttons.  Call buttons in elevator lobbies and 
  642. halls shall be centered at 42 in (1065 mm) above the floor.  Such 
  643. call buttons shall have visual signals to indicate when each call 
  644. is registered and when each call is answered.  Call buttons shall 
  645. be a minimum of 3/4 in (19 mm) in the smallest dimension.  The 
  646. button designating the up direction shall be on top.  (See Fig.  
  647. 20.) Buttons shall be raised or flush.  Objects mounted beneath 
  648. hall call buttons shall not project into the elevator lobby more 
  649. than 4 in (100 mm).
  650.  
  651. 4.10.4 Hall Lanterns.  A visible and audible signal shall be 
  652. provided at each hoistway entrance to indicate which car is 
  653. answering a call.  Audible signals shall sound once for the up 
  654. direction and twice for the down direction or shall have verbal 
  655. annunciators that say "up" or "down." Visible signals shall have 
  656. the following features:
  657.  
  658.  (1) Hall lantern fixtures shall be mounted so that their 
  659. centerline is at least 72 in (1830 mm) above the lobby floor.  
  660. (See Fig. 20.)
  661.  
  662.  (2) Visual elements shall be at least 2-1/2 in (64 mm) in 
  663. the smallest dimension.
  664.  
  665.  (3) Signals shall be visible from the vicinity of the hall 
  666. call button (see Fig. 20).  In-car lanterns located in cars, 
  667. visible from the vicinity of hall call buttons, and conforming to 
  668. the above requirements, shall be acceptable.
  669.  
  670. 4.10.5 Raised and Braille Characters on Hoistway Entrances.  All 
  671. elevator hoistway entrances shall have raised and Braille floor 
  672. designations provided on both jambs.  The centerline of the 
  673. characters shall be 60 in (1525 mm) above finish floor.  Such 
  674. characters shall be 2 in (50 mm) high and shall comply with 
  675. 4.30.4.  Permanently applied plates are acceptable if they are 
  676. permanently fixed to the jambs.  (See Fig. 20).
  677.  
  678. 4.10.6* Door Protective and Reopening Device.  Elevator doors 
  679. shall open and close automatically.  They shall be provided with 
  680. a reopening device that will stop and reopen a car door and 
  681. hoistway door automatically if the door becomes obstructed by an 
  682. object or person.  The device shall be capable of completing 
  683. these operations without requiring contact for an obstruction 
  684. passing through the opening at heights of 5 in and 29 in (125 mm 
  685. and 735 mm) above finish floor (see Fig. 20).  Door reopening 
  686. devices shall remain effective for at least 20 seconds.  After 
  687. such an interval, doors may close in accordance with the 
  688. requirements of ASME A17.1-1990.
  689.  
  690. 4.10.7* Door and Signal Timing for Hall Calls.  The minimum 
  691. acceptable time from notification that a car is answering a call 
  692. until the doors of that car start to close shall be calculated 
  693. from the following equation:
  694.  
  695. T = D/(1.5 ft/s) or T = D/(445 mm/s)
  696.  
  697. where T total time in seconds and D distance (in feet or 
  698. millimeters) from a point in the lobby or corridor 60 in (1525 
  699. mm) directly in front of the farthest call button controlling 
  700. that car to the centerline of its hoistway door (see Fig. 21).  
  701. For cars with in-car lanterns, T begins when the lantern is 
  702. visible from the vicinity of hall call buttons and an audible 
  703. signal is sounded.  The minimum acceptable notification time 
  704. shall be 5 seconds.
  705.  
  706. 4.10.8 Door Delay for Car Calls.  The minimum time for elevator 
  707. doors to remain fully open in response to a car call shall be 3 
  708. seconds.
  709.  
  710. 4.10.9 Floor Plan of Elevator Cars.  The floor area of elevator 
  711. cars shall provide space for wheelchair users to enter the car, 
  712. maneuver within reach of controls, and exit from the car.  
  713. Acceptable door opening and inside dimensions shall be as shown 
  714. in Fig. 22.  The clearance between the car platform sill and the 
  715. edge of any hoistway landing shall be no greater than 1-1/4 in 
  716. (32 mm).
  717.  
  718. 4.10.10 Floor Surfaces.  Floor surfaces shall comply with 4.5.
  719.  
  720. 4.10.11 Illumination Levels.  The level of illumination at the 
  721. car controls, platform, and car threshold and landing sill shall 
  722. be at least 5 footcandles (53.8 lux).
  723.  
  724. 4.10.12* Car Controls.  Elevator control panels shall have the 
  725. following features:
  726.  
  727.  (1) Buttons.  All control buttons shall be at least 3/4 in 
  728. (19 mm) in their smallest dimension.  They shall be raised or 
  729. flush.
  730.  
  731.  (2) Tactile, Braille, and Visual Control Indicators.  All 
  732. control buttons shall be designated by Braille and by raised 
  733. standard alphabet characters for letters, arabic characters for 
  734. numerals, or standard symbols as shown in Fig. 23(a), and as 
  735. required in ASME A17.1-1990.  Raised and Braille characters and 
  736. symbols shall comply with 4.30.  The call button for the main 
  737. entry floor shall be designated by a raised star at the left of 
  738. the floor designation (see Fig. 23(a)).  All raised designations 
  739. for control buttons shall be placed immediately to the left of 
  740. the button to which they apply.  Applied plates, permanently 
  741. attached, are an acceptable means to provide raised control 
  742. designations.  Floor buttons shall be provided with visual 
  743. indicators to show when each call is registered.  The visual 
  744. indicators shall be extinguished when each call is answered.
  745.  
  746.  (3) Height.  All floor buttons shall be no higher than 54 
  747. in (1370 mm) above the finish floor for side approach and 48 in 
  748. (1220 mm) for front approach.  Emergency controls, including the 
  749. emergency alarm and emergency stop, shall be grouped at the 
  750. bottom of the panel and shall have their centerlines no less than 
  751. 35 in (890 mm) above the finish floor (see Fig. 23(a) and (b)).
  752.  (4) Location.  Controls shall be located on a front wall 
  753. if cars have center opening doors, and at the side wall or at the 
  754. front wall next to the door if cars have side opening doors (see 
  755. Fig.  23(c) and (d)).
  756.  
  757. 4.10.13* Car Position Indicators.  In elevator cars, a visual car 
  758. position indicator shall be provided above the car control panel 
  759. or over the door to show the position of the elevator in the 
  760. hoistway.  As the car passes or stops at a floor served by the 
  761. elevators, the corresponding numerals shall illuminate, and an 
  762. audible signal shall sound.  Numerals shall be a minimum of 1/2 
  763. in (13 mm) high.  The audible signal shall be no less than 20 
  764. decibels with a frequency no higher than 1500 Hz.  An automatic 
  765. verbal announcement of the floor number at which a car stops or 
  766. which a car passes may be substituted for the audible signal.
  767.  
  768. 4.10.14* Emergency Communications.  If provided, emergency 
  769. two-way communication systems between the elevator and a point 
  770. outside the hoistway shall comply with ASME A17.1-1990.  The 
  771. highest operable part of a two-way communication system shall be 
  772. a maximum of 48 in (1220 mm) from the floor of the car.  It shall 
  773. be identified by a raised symbol and lettering complying with 
  774. 4.30 and located adjacent to the device.  If the system uses a 
  775. handset then the length of the cord from the panel to the handset 
  776. shall be at least 29 in (735 mm).  If the system is located in a 
  777. closed compartment the compartment door hardware shall conform to 
  778. 4.27, Controls and Operating Mechanisms.  The emergency 
  779. intercommunication system shall not require voice communication.
  780.  
  781. 4.11 Platform Lifts (Wheelchair Lifts).
  782.  
  783. 4.11.1 Location.  Platform lifts (wheelchair lifts) permitted by 
  784. 4.1 shall comply with the requirements of 4.11.
  785.  
  786. 4.11.2* Other Requirements.  If platform lifts (wheelchair lifts) 
  787. are used, they shall comply with 4.2.4, 4.5, 4.27, and ASME A17.1 
  788. Safety Code for Elevators and Escalators, Section XX, 1990.
  789.  
  790. 4.11.3 Entrance.  If platform lifts are used then they shall 
  791. facilitate unassisted entry, operation, and exit from the lift in 
  792. compliance with 4.11.2.
  793.  
  794. 4.12 Windows.
  795.  
  796. 4.12.1* General.  (Reserved).
  797.  
  798. 4.12.2* Window Hardware.  (Reserved).
  799.  
  800. 4.13 Doors.
  801.  
  802. 4.13.1 General.  Doors required to be accessible by 4.1 shall 
  803. comply with the requirements of 4.13.
  804.  
  805. 4.13.2 Revolving Doors and Turnstiles.  Revolving doors or 
  806. turnstiles shall not be the only means of passage at an 
  807. accessible entrance or along an accessible route.  An accessible 
  808. gate or door shall be provided adjacent to the turnstile or 
  809. revolving door and shall be so designed as to facilitate the same 
  810. use pattern.
  811.  
  812. 4.13.3 Gates.  Gates, including ticket gates, shall meet all 
  813. applicable specifications of 4.13.
  814.  
  815. 4.13.4 Double-Leaf Doorways.  If doorways have two independently 
  816. operated door leaves, then at least one leaf shall meet the 
  817. specifications in 4.13.5 and 4.13.6.  That leaf shall be an 
  818. active leaf.
  819.  
  820. 4.13.5 Clear Width.  Doorways shall have a minimum clear opening 
  821. of 32 in (815 mm) with the door open 90 degrees, measured between 
  822. the face of the door and the opposite stop (see Fig. 24(a), (b), 
  823. (c), and (d)).  Openings more than 24 in (610 mm) in depth shall 
  824. comply with 4.2.1 and 4.3.3 (see Fig. 24(e)).
  825.  
  826. EXCEPTION: Doors not requiring full user passage, such as shallow 
  827. closets, may have the clear opening reduced to 20 in (510 mm) 
  828. minimum.
  829.  
  830. 4.13.6 Maneuvering Clearances at Doors.  Minimum maneuvering 
  831. clearances at doors that are not automatic or power-assisted 
  832. shall be as shown in Fig. 25.  The floor or ground area within 
  833. the required clearances shall be level and clear.
  834.  
  835. EXCEPTION: Entry doors to acute care hospital bedrooms for 
  836. in-patients shall be exempted from the requirement for space at 
  837. the latch side of the door (see dimension "x" in Fig. 25) if the 
  838. door is at least 44 in (1120 mm) wide.
  839.  
  840. 4.13.7 Two Doors in Series.  The minimum space between two hinged 
  841. or pivoted doors in series shall be 48 in (1220 mm) plus the 
  842. width of any door swinging into the space.  Doors in series shall 
  843. swing either in the same direction or away from the space between 
  844. the doors (see Fig. 26).
  845.  
  846. 4.13.8* Thresholds at Doorways.  Thresholds at doorways shall not 
  847. exceed 3/4 in (19 mm) in height for exterior sliding doors or 1/2 
  848. in (13 mm) for other types of doors.  Raised thresholds and floor 
  849. level changes at accessible doorways shall be beveled with a 
  850. slope no greater than 1:2 (see 4.5.2).
  851.  
  852. 4.13.9* Door Hardware.  Handles, pulls, latches, locks, and other 
  853. operating devices on accessible doors shall have a shape that is 
  854. easy to grasp with one hand and does not require tight grasping, 
  855. tight pinching, or twisting of the wrist to operate.  
  856. Lever-operated mechanisms, push-type mechanisms, and U-shaped 
  857. handles are acceptable designs.  When sliding doors are fully 
  858. open, operating hardware shall be exposed and usable from both 
  859. sides.  Hardware required for accessible door passage shall be 
  860. mounted no higher than 48 in (1220 mm) above finished floor.
  861.  
  862. 4.13.10* Door Closers.  If a door has a closer, then the sweep 
  863. period of the closer shall be adjusted so that from an open 
  864. position of 70 degrees, the door will take at least 3 seconds to 
  865. move to a point 3 in (75 mm) from the latch, measured to the 
  866. leading edge of the door.
  867.  
  868. 4.13.11* Door Opening Force.  The maximum force for pushing or 
  869. pulling open a door shall be as follows:
  870.  
  871.  (1) Fire doors shall have the minimum opening force 
  872. allowable by the appropriate administrative authority.
  873.  
  874.  (2) Other doors.
  875.  
  876.  (a) exterior hinged doors:  (Reserved).
  877.  
  878.  (b) interior hinged doors: 5 lbf (22.2N)
  879.  
  880.  (c) sliding or folding doors: 5 lbf (22.2N)
  881.  
  882. These forces do not apply to the force required to retract latch 
  883. bolts or disengage other devices that may hold the door in a 
  884. closed position.
  885.  
  886. 4.13.12* Automatic Doors and Power-Assisted Doors.  If an 
  887. automatic door is used, then it shall comply with ANSI/BHMA 
  888. A156.10-1985.  Slowly opening, low-powered, automatic doors shall 
  889. comply with ANSI A156.19-1984.  Such doors shall not open to back 
  890. check faster than 3 seconds and shall require no more than 15 lbf 
  891. (66.6N) to stop door movement.  If a power-assisted door is used, 
  892. its door-opening force shall comply with 4.13.11 and its closing 
  893. shall conform to the requirements in ANSI A156.19-1984.
  894.  
  895. 4.14 Entrances.
  896.  
  897. 4.14.1 Minimum Number.  Entrances required to be accessible by 
  898. 4.1 shall be part of an accessible route complying with 4.3.  
  899. Such entrances shall be connected by an accessible route to 
  900. public transportation stops, to accessible parking and passenger 
  901. loading zones, and to public streets or sidewalks if available 
  902. (see 4.3.2(1)).  They shall also be connected by an accessible 
  903. route to all accessible spaces or elements within the building or 
  904. facility.
  905.  
  906. 4.14.2 Service Entrances.  A service entrance shall not be the 
  907. sole accessible entrance unless it is the only entrance to a 
  908. building or facility (for example, in a factory or garage).
  909.  
  910. 4.15 Drinking Fountains and Water Coolers.
  911.  
  912. 4.15.1 Minimum Number.  Drinking fountains or water coolers 
  913. required to be accessible by 4.1 shall comply with 4.15.
  914.  
  915. 4.15.2* Spout Height.  Spouts shall be no higher than 36 in (915 
  916. mm), measured from the floor or ground surfaces to the spout 
  917. outlet (see Fig. 27(a)).
  918.  
  919. 4.15.3 Spout Location.  The spouts of drinking fountains and 
  920. water coolers shall be at the front of the unit and shall direct 
  921. the water flow in a trajectory that is parallel or nearly 
  922. parallel to the front of the unit.  The spout shall provide a 
  923. flow of water at least 4 in (100 mm) high so as to allow the 
  924. insertion of a cup or glass under the flow of water.  On an 
  925. accessible drinking fountain with a round or oval bowl, the spout 
  926. must be positioned so the flow of water is within 3 in (75 mm) of 
  927. the front edge of the fountain.
  928.  
  929. 4.15.4 Controls.  Controls shall comply with 4.27.4.  Unit 
  930. controls shall be front mounted or side mounted near the front 
  931. edge.
  932.  
  933. 4.15.5 Clearances.
  934.  
  935.  (1) Wall- and post-mounted cantilevered units shall have a 
  936. clear knee space between the bottom of the apron and the floor or 
  937. ground at least 27 in (685 mm) high, 30 in (760 mm) wide, and 17 
  938. in to 19 in (430 mm to 485 mm) deep (see Fig. 27(a) and (b)).  
  939. Such units shall also have a minimum clear floor space 30 in by 
  940. 48 in (760 mm by 1220 mm) to allow a person in a wheelchair to 
  941. approach the unit facing forward.
  942.  
  943.  (2) Free-standing or built-in units not having a clear 
  944. space under them shall have a clear floor space at least 30 in by 
  945. 48 in (760 mm by 1220 mm) that allows a person in a wheelchair to 
  946. make a parallel approach to the unit (see Fig. 27(c) and (d)).  
  947. This clear floor space shall comply with 4.2.4.
  948.  
  949. 4.16 Water Closets.
  950.  
  951. 4.16.1 General.  Accessible water closets shall comply with 4.16.
  952.  
  953. 4.16.2 Clear Floor Space.  Clear floor space for water closets 
  954. not in stalls shall comply with Fig. 28.  Clear floor space may 
  955. be arranged to allow either a left-handed or right-handed 
  956. approach.
  957.  
  958. 4.16.3* Height.  The height of water closets shall be 17 in to 19 
  959. in (430 mm to 485 mm), measured to the top of the toilet seat 
  960. (see Fig. 29(b)).  Seats shall not be sprung to return to a 
  961. lifted position.
  962.  
  963. 4.16.4* Grab Bars.  Grab bars for water closets not located in 
  964. stalls shall comply with 4.26 and Fig. 29.  The grab bar behind 
  965. the water closet shall be 36 in (915 mm) minimum.
  966.  
  967. 4.16.5* Flush Controls.  Flush controls shall be hand operated or 
  968. automatic and shall comply with 4.27.4.  Controls for flush 
  969. valves shall be mounted on the wide side of toilet areas no more 
  970. than 44 in (1120 mm) above the floor.
  971.  
  972. 4.16.6 Dispensers.  Toilet paper dispensers shall be installed 
  973. within reach, as shown in Fig. 29(b).  Dispensers that control 
  974. delivery, or that do not permit continuous paper flow, shall not 
  975. be used.
  976.  
  977. 4.17 Toilet Stalls.
  978.  
  979. 4.17.1 Location.  Accessible toilet stalls shall be on an 
  980. accessible route and shall meet the requirements of 4.17.
  981.  
  982. 4.17.2 Water Closets.  Water closets in accessible stalls shall 
  983. comply with 4.16.
  984.  
  985. 4.17.3* Size and Arrangement.  The size and arrangement of the 
  986. standard toilet stall shall comply with Fig. 30(a), Standard 
  987. Stall.  Standard toilet stalls with a minimum depth of 56 in 
  988. (1420 mm) (see Fig. 30(a)) shall have wall-mounted water closets.  
  989. If the depth of a standard toilet stall is increased at least 3 
  990. in (75 mm), then a floor-mounted water closet may be used.  
  991. Arrangements shown for standard toilet stalls may be reversed to 
  992. allow either a left- or right-hand approach.  Additional stalls 
  993. shall be provided in conformance with 4.22.4.
  994.  
  995. EXCEPTION: In instances of alteration work where provision of a 
  996. standard stall (Fig. 30(a)) is technically infeasible or where 
  997. plumbing code requirements prevent combining existing stalls to 
  998. provide space, either alternate stall (Fig. 30(b)) may be 
  999. provided in lieu of the standard stall.
  1000.  
  1001. 4.17.4 Toe Clearances.  In standard stalls, the front partition 
  1002. and at least one side partition shall provide a toe clearance of 
  1003. at least 9 in (230 mm) above the floor.  If the depth of the 
  1004. stall is greater than 60 in (1525 mm), then the toe clearance is 
  1005. not required.
  1006.  
  1007. 4.17.5* Doors.  Toilet stall doors, including door hardware, 
  1008. shall comply with 4.13.  If toilet stall approach is from the 
  1009. latch side of the stall door, clearance between the door side of 
  1010. the stall and any obstruction may be reduced to a minimum of 42 
  1011. in (1065 mm) (Fig. 30).
  1012.  
  1013. 4.17.6 Grab Bars.  Grab bars complying with the length and 
  1014. positioning shown in Fig. 30(a), (b), (c), and (d) shall be 
  1015. provided.  Grab bars may be mounted with any desired method as 
  1016. long as they have a gripping surface at the locations shown and 
  1017. do not obstruct the required clear floor area.  Grab bars shall 
  1018. comply with 4.26.
  1019.  
  1020. 4.18 Urinals.
  1021.  
  1022. 4.18.1 General.  Accessible urinals shall comply with 4.18.
  1023.  
  1024. 4.18.2 Height.  Urinals shall be stall-type or wall-hung with an 
  1025. elongated rim at a maximum of 17 in (430 mm) above the finish 
  1026. floor.
  1027.  
  1028. 4.18.3 Clear Floor Space.  A clear floor space 30 in by 48 in 
  1029. (760 mm by 1220 mm) shall be provided in front of urinals to 
  1030. allow forward approach.  This clear space shall adjoin or overlap 
  1031. an accessible route and shall comply with 4.2.4.  Urinal shields 
  1032. that do not extend beyond the front edge of the urinal rim may be 
  1033. provided with 29 in (735 mm) clearance between them.
  1034.  
  1035. 4.18.4 Flush Controls.  Flush controls shall be hand operated or 
  1036. automatic, and shall comply with 4.27.4, and shall be mounted no 
  1037. more than 44 in (1120 mm) above the finish floor.
  1038.  
  1039. 4.19 Lavatories and Mirrors.
  1040.  
  1041. 4.19.1 General.  The requirements of 4.19 shall apply to lavatory 
  1042. fixtures, vanities, and built-in lavatories.
  1043.  
  1044. 4.19.2 Height and Clearances.  Lavatories shall be mounted with 
  1045. the rim or counter surface no higher than 34 in (865 mm) above 
  1046. the finish floor.  Provide a clearance of at least 29 in (735 mm) 
  1047. above the finish floor to the bottom of the apron.  Knee and toe 
  1048. clearance shall comply with Fig. 31.
  1049.  
  1050. 4.19.3 Clear Floor Space.  A clear floor space 30 in by 48 in 
  1051. (760 mm by 1220 mm) complying with 4.2.4 shall be provided in 
  1052. front of a lavatory to allow forward approach.  Such clear floor 
  1053. space shall adjoin or overlap an accessible route and shall 
  1054. extend a maximum of 19 in (485 mm) underneath the lavatory (see 
  1055. Fig. 32).
  1056.  
  1057. 4.19.4 Exposed Pipes and Surfaces.  Hot water and drain pipes 
  1058. under lavatories shall be insulated or otherwise configured to 
  1059. protect against contact.  There shall be no sharp or abrasive 
  1060. surfaces under lavatories.
  1061.  
  1062. 4.19.5 Faucets.  Faucets shall comply with 4.27.4.  
  1063. Lever-operated, push-type, and electronically controlled 
  1064. mechanisms are examples of acceptable designs.  If self-closing 
  1065. valves are used the faucet shall remain open for at least 10 
  1066. seconds.
  1067.  
  1068. 4.19.6* Mirrors.  Mirrors shall be mounted with the bottom edge 
  1069. of the reflecting surface no higher than 40 in (1015 mm) above 
  1070. the finish floor (see Fig. 31).
  1071.  
  1072. 4.20 Bathtubs.
  1073.  
  1074. 4.20.1 General.  Accessible bathtubs shall comply with 4.20.
  1075.  
  1076. 4.20.2 Floor Space.  Clear floor space in front of bathtubs shall 
  1077. be as shown in Fig. 33.
  1078.  
  1079. 4.20.3 Seat.  An in-tub seat or a seat at the head end of the tub 
  1080. shall be provided as shown in Fig. 33 and 34.  The structural 
  1081. strength of seats and their attachments shall comply with 4.26.3.  
  1082. Seats shall be mounted securely and shall not slip during use.
  1083.  
  1084. 4.20.4 Grab Bars.  Grab bars complying with 4.26 shall be 
  1085. provided as shown in Fig. 33 and 34.
  1086.  
  1087. 4.20.5 Controls.  Faucets and other controls complying with 
  1088. 4.27.4 shall be located as shown in Fig. 34.
  1089.  
  1090. 4.20.6 Shower Unit.  A shower spray unit with a hose at least 60 
  1091. in (1525 mm) long that can be used both as a fixed shower head 
  1092. and as a hand-held shower shall be provided.
  1093.  
  1094. 4.20.7 Bathtub Enclosures.  If provided, enclosures for bathtubs 
  1095. shall not obstruct controls or transfer from wheelchairs onto 
  1096. bathtub seats or into tubs.  Enclosures on bathtubs shall not 
  1097. have tracks mounted on their rims.
  1098.  
  1099. 4.21 Shower Stalls.
  1100.  
  1101. 4.21.1* General.  Accessible shower stalls shall comply with 
  1102. 4.21.
  1103.  
  1104. 4.21.2 Size and Clearances.  Except as specified in 9.1.2, shower 
  1105. stall size and clear floor space shall comply with Fig. 35(a) or 
  1106. (b).  The shower stall in Fig. 35(a) shall be 36 in by 36 in (915 
  1107. mm by 915 mm).  Shower stalls required by 9.1.2 shall comply with 
  1108. Fig. 57(a) or (b).  The shower stall in Fig. 35(b) will fit into 
  1109. the space required for a bathtub.
  1110.  
  1111. 4.21.3 Seat.  A seat shall be provided in shower stalls 36 in by 
  1112. 36 in (915 mm by 915 mm) and shall be as shown in Fig. 36.  The 
  1113. seat shall be mounted 17 in to 19 in (430 mm to 485 mm) from the 
  1114. bathroom floor and shall extend the full depth of the stall.  In 
  1115. a 36 in by 36 in (915 mm by 915 mm) shower stall, the seat shall 
  1116. be on the wall opposite the controls.  Where a fixed seat is 
  1117. provided in a 30 in by 60 in minimum (760 mm by 1525 mm) shower 
  1118. stall, it shall be a folding type and shall be mounted on the 
  1119. wall adjacent to the controls as shown in Fig. 57.  The 
  1120. structural strength of seats and their attachments shall comply 
  1121. with 4.26.3.
  1122.  
  1123. 4.21.4 Grab Bars.  Grab bars complying with 4.26 shall be 
  1124. provided as shown in Fig. 37.
  1125.  
  1126. 4.21.5 Controls.  Faucets and other controls complying with 
  1127. 4.27.4 shall be located as shown in Fig. 37.  In shower stalls 36 
  1128. in by 36 in (915 mm by 915 mm), all controls, faucets, and the 
  1129. shower unit shall be mounted on the side wall opposite the seat.
  1130.  
  1131. 4.21.6 Shower Unit.  A shower spray unit with a hose at least 60 
  1132. in (1525 mm) long that can be used both as a fixed shower head 
  1133. and as a hand-held shower shall be provided.
  1134.  
  1135. EXCEPTION: In unmonitored facilities where vandalism is a 
  1136. consideration, a fixed shower head mounted at 48 in (1220 mm) 
  1137. above the shower floor may be used in lieu of a hand-held shower 
  1138. head.
  1139.  
  1140. 4.21.7 Curbs.  If provided, curbs in shower stalls 36 in by 36 in 
  1141. (915 mm by 915 mm) shall be no higher than 1/2 in (13 mm).  
  1142. Shower stalls that are 30 in by 60 in (760 mm by 1525 mm) minimum 
  1143. shall not have curbs.
  1144.  
  1145. 4.21.8 Shower Enclosures.  If provided, enclosures for shower 
  1146. stalls shall not obstruct controls or obstruct transfer from 
  1147. wheelchairs onto shower seats.
  1148.  
  1149. 4.22 Toilet Rooms.
  1150.  
  1151. 4.22.1 Minimum Number.  Toilet facilities required to be 
  1152. accessible by 4.1 shall comply with 4.22.  Accessible toilet 
  1153. rooms shall be on an accessible route.
  1154.  
  1155. 4.22.2 Doors.  All doors to accessible toilet rooms shall comply 
  1156. with 4.13.  Doors shall not swing into the clear floor space 
  1157. required for any fixture.
  1158.  
  1159. 4.22.3* Clear Floor Space.  The accessible fixtures and controls 
  1160. required in 4.22.4, 4.22.5, 4.22.6, and 4.22.7 shall be on an 
  1161. accessible route.  An unobstructed turning space complying with 
  1162. 4.2.3 shall be provided within an accessible toilet room.  The 
  1163. clear floor space at fixtures and controls, the accessible route, 
  1164. and the turning space may overlap.
  1165.  
  1166. 4.22.4 Water Closets.  If toilet stalls are provided, then at 
  1167. least one shall be a standard toilet stall complying with 4.17; 
  1168. where 6 or more stalls are provided, in addition to the stall 
  1169. complying with 4.17.3, at least one stall 36 in (915 mm) wide 
  1170. with an outward swinging, self-closing door and parallel grab 
  1171. bars complying with Fig. 30(d) and 4.26 shall be provided.  Water 
  1172. closets in such stalls shall comply with 4.16.  If water closets 
  1173. are not in stalls, then at least one shall comply with 4.16.
  1174.  
  1175. 4.22.5 Urinals.  If urinals are provided, then at least one shall 
  1176. comply with 4.18.
  1177.  
  1178. 4.22.6 Lavatories and Mirrors.  If lavatories and mirrors are 
  1179. provided, then at least one of each shall comply with 4.19.
  1180.  
  1181. 4.22.7 Controls and Dispensers.  If controls, dispensers, 
  1182. receptacles, or other equipment are provided, then at least one 
  1183. of each shall be on an accessible route and shall comply with 
  1184. 4.27.
  1185.  
  1186. 4.23 Bathrooms, Bathing Facilities, and Shower Rooms.
  1187.  
  1188. 4.23.1 Minimum Number.  Bathrooms, bathing facilities, or shower 
  1189. rooms required to be accessible by 4.1 shall comply with 4.23 and 
  1190. shall be on an accessible route.
  1191.  
  1192. 4.23.2 Doors.  Doors to accessible bathrooms shall comply with
  1193. 4.13. Doors shall not swing into the floor space required for any 
  1194. fixture.
  1195.  
  1196. 4.23.3* Clear Floor Space.  The accessible fixtures and controls 
  1197. required in 4.23.4, 4.23.5, 4.23.6, 4.23.7, 4.23.8, and 4.23.9 
  1198. shall be on an accessible route.  An unobstructed turning space 
  1199. complying with 4.2.3 shall be provided within an accessible 
  1200. bathroom.  The clear floor spaces at fixtures and controls, the 
  1201. accessible route, and the turning space may overlap.
  1202.  
  1203. 4.23.4 Water Closets.  If toilet stalls are provided, then at 
  1204. least one shall be a standard toilet stall complying with 4.17; 
  1205. where 6 or more stalls are provided, in addition to the stall 
  1206. complying with 4.17.3, at least one stall 36 in (915 mm) wide 
  1207. with an outward swinging, self-closing door and parallel grab 
  1208. bars complying with Fig. 30(d) and 4.26 shall be provided.  Water 
  1209. closets in such stalls shall comply with 4.16.  If water closets 
  1210. are not in stalls, then at least one shall comply with 4.16.
  1211.  
  1212. 4.23.5 Urinals.  If urinals are provided, then at least one shall 
  1213. comply with 4.18.
  1214.  
  1215. 4.23.6 Lavatories and Mirrors.  If lavatories and mirrors are 
  1216. provided, then at least one of each shall comply with 4.19.
  1217.  
  1218. 4.23.7 Controls and Dispensers.  If controls, dispensers, 
  1219. receptacles, or other equipment are provided, then at least one 
  1220. of each shall be on an accessible route and shall comply with 
  1221. 4.27.
  1222.  
  1223. 4.23.8 Bathing and Shower Facilities.  If tubs or showers are 
  1224. provided, then at least one accessible tub that complies with 
  1225. 4.20 or at least one accessible shower that complies with 4.21 
  1226. shall be provided.
  1227.  
  1228. 4.23.9* Medicine Cabinets.  If medicine cabinets are provided, at 
  1229. least one shall be located with a usable shelf no higher than 44 
  1230. in (1120 mm) above the floor space.  The floor space shall comply 
  1231. with 4.2.4.
  1232.  
  1233. 4.24 Sinks.
  1234.  
  1235. 4.24.1 General.  Sinks required to be accessible by 4.1 shall 
  1236. comply with 4.24.
  1237.  
  1238. 4.24.2 Height.  Sinks shall be mounted with the counter or rim no 
  1239. higher than 34 in (865 mm) above the finish floor.
  1240.  
  1241. 4.24.3 Knee Clearance.  Knee clearance that is at least 27 in 
  1242. (685 mm) high, 30 in (760 mm) wide, and 19 in (485 mm) deep shall 
  1243. be provided underneath sinks.
  1244.  
  1245. 4.24.4 Depth.  Each sink shall be a maximum of 6-1/2 in (165 mm) 
  1246. deep.
  1247.  
  1248. 4.24.5 Clear Floor Space.  A clear floor space at least 30 in by 
  1249. 48 in (760 mm by 1220 mm) complying with 4.2.4 shall be provided 
  1250. in front of a sink to allow forward approach.  The clear floor 
  1251. space shall be on an accessible route and shall extend a maximum 
  1252. of 19 in (485 mm) underneath the sink (see Fig. 32).
  1253.  
  1254. 4.24.6 Exposed Pipes and Surfaces.  Hot water and drain pipes 
  1255. exposed under sinks shall be insulated or otherwise configured so 
  1256. as to protect against contact.  There shall be no sharp or 
  1257. abrasive surfaces under sinks.
  1258.  
  1259. 4.24.7 Faucets.  Faucets shall comply with 4.27.4.  
  1260. Lever-operated, push-type, touch-type, or electronically 
  1261. controlled mechanisms are acceptable designs.
  1262.  
  1263. 4.25 Storage.
  1264.  
  1265. 4.25.1 General.  Fixed storage facilities such as cabinets, 
  1266. shelves, closets, and drawers required to be accessible by 4.1 
  1267. shall comply with 4.25.
  1268.  
  1269. 4.25.2 Clear Floor Space.  A clear floor space at least 30 in by 
  1270. 48 in (760 mm by 1220 mm) complying with 4.2.4 that allows either 
  1271. a forward or parallel approach by a person using a wheelchair 
  1272. shall be provided at accessible storage facilities.
  1273.  
  1274. 4.25.3 Height.  Accessible storage spaces shall be within at 
  1275. least one of the reach ranges specified in 4.2.5 and 4.2.6 (see 
  1276. Fig. 5 and Fig 6).  Clothes rods or shelves shall be a maximum of 
  1277. 54 in (1370 mm) above the finish floor for a side approach.  
  1278. Where the distance from the wheelchair to the clothes rod or 
  1279. shelf exceeds 10 in (255 mm) (as in closets without accessible 
  1280. doors) the height and depth to the rod or shelf shall comply with 
  1281. Fig. 38(a) and Fig. 38(b).
  1282.  
  1283. 4.25.4 Hardware.  Hardware for accessible storage facilities 
  1284. shall comply with 4.27.4.  Touch latches and U-shaped pulls are 
  1285. acceptable.
  1286.  
  1287. 4.26 Handrails, Grab Bars, and Tub and Shower Seats.
  1288.  
  1289. 4.26.1* General.  All handrails, grab bars, and tub and shower 
  1290. seats required to be accessible by 4.1, 4.8, 4.9, 4.16, 4.17, 
  1291. 4.20 or 4.21 shall comply with 4.26.
  1292.  
  1293. 4.26.2* Size and Spacing of Grab Bars and Handrails.  The 
  1294. diameter or width of the gripping surfaces of a handrail or grab 
  1295. bar shall be 1-1/4 in to 1-1/2 in (32 mm to 38 mm), or the shape 
  1296. shall provide an equivalent gripping surface.  If handrails or 
  1297. grab bars are mounted adjacent to a wall, the space between the 
  1298. wall and the grab bar shall be 1-1/2 in (38 mm) (see Fig. 39(a), 
  1299. (b), (c), and (e)).  Handrails may be located in a recess if the 
  1300. recess is a maximum of 3 in (75 mm) deep and extends at least 18 
  1301. in (455 mm) above the top of the rail (see Fig. 39(d)).
  1302.  
  1303. 4.26.3 Structural Strength.  The structural strength of grab 
  1304. bars, tub and shower seats, fasteners, and mounting devices shall 
  1305. meet the following specification:
  1306.